PROMPTEXPLANATION

ENTER ZONE NO.

 

00 = QUIT

11

The system now returns to the “ENTER ZONE NO.” prompt for the next zone. When all zones have been programmed, enter 00 to quit.

After you have enrolled each wireless device, remove ONE of the serial number labels from that device and affix it in the appropriate column on the worksheets provided later in this Programming Guide; then enter the other information (zone number, zone type, etc.) relevant to that device.

When you have finished programming all zones, test each using the system’s Test Mode. Do not use the Transmitter ID Sniffer Mode. The system checks only for transmission of one zone on a particular transmitter, NOT the zones assigned to each additional loop, and also does not verify polling loop type zones.

Expert Mode Zone Programming

Expert mode allows you to program zones using the minimum number of screens and keystrokes. Enter the Programming mode with [Installer Code] + [8] [0] [0]

Before programming your zones, do the following:

1.Program field 200: Number of Partitions.

2.Enable your RF Receiver in Device Programming menu mode.

To program your zones, press 93 to display the "ZONE PROG?" prompt. Enter 0 (NO) to each prompt until the “EXPERT MODE?” prompt appears.

PROMPTEXPLANATION

 

EXPERT MODE?

 

 

1 = YES

0 = NO

0

 

 

 

 

 

 

 

 

SET TO CONFIRM?

 

 

0 = NO

1 = YES

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zn

ZT

P RC

In

L

 

01

03 1 10 HW

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zn

ZT

P

RC

In

L

 

10

03

1

10

RF

1s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zn

ZT

P

RC

In

L

 

10

03

1

10

RF

-

 

Press 1 to enter Expert mode.

This prompt appears once upon entering Expert Mode.

If you select “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have been entered later.

A summary display appears, showing zone 1’s current programming or default values.

Enter the desired 2-digit zone number and press []. Note: If you want to exit the Expert mode, enter 00 + [].

If an “s” appears after the loop number, it indicates that the transmitter’s serial number has been enrolled. Use the [D] key to enter and duplicate wireless keys (see “Entering Wireless Keys” later)

Enter all zone information except for Loop number, or press [C] to copy the zone information on this screen from the last saved zone (including Loop).

ZT = Zone Type

P= Partition RC = Report Code

In = Input Device Type

L = Loop number to which the sensor is connected.

NOTE: Pressing the [C] copies the zone information from the last saved zone, which includes the input type. Verify this information is correct for this zone.

On this screen:

Use the [A] key to move to the right.

Use the [B] key to move to left and to back up to “ZT” field. Press [] to accept the existing or newly entered zone information.

– 14 –

Page 14
Image 14
Honeywell VISTA-40 Expert Mode Zone Programming, Program field 200 Number of Partitions, Enter Zone no, SET to CONFIRM?