Relay Output Devices Programming

Relay Output Devices Programming

From Data Field Programming Mode, press #93 to display the "ZONE PROG?" prompt. Press [0] (NO) to each menu option until the "RELAY PROG?" prompt appears. Press [1] (YES).

While in this mode, press [] to advance to next screen. Press [#] to back up to the previous screen.

PROMPTEXPLANATION

ENTER RELAY #

(00=QUIT) 01

02 A EV ZL P STT 0 0 00 0

02A ZL ZT P STOP 0 00 00 0

 

02

RELAY ACTION

 

 

NO RESPONSE

0

 

 

 

 

 

 

 

 

 

 

02

START EVENT

 

 

NOT USED

0

 

Enter the relay (output device) identification number 01-08. This is a reference number only, used for identification purposes. The actual module address and relay number on the module are programmed in the last two prompts.

Press [] to continue.

Press [] to continue.

The keypad displays a summary STOP screen.

Press [] to continue.

The Relay Action is the way in which the relay will respond when activated by the "start" event. Enter the desired action for this relay as follows:

0=not used; 1=close for 2 secs.; 2=stay closed; 3=pulse on/off

A relay may be activated by an Event/Zone List combination, and/or by a Zone Type/System Operation. For an Event/Zone List combination, enter the event code as follows:

0=not used; 1=alarm; 2=fault; 3=trouble

If you are not using a Zone List to activate the relay, enter 0. Press [] to continue.

 

02

START: ZN LIST

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

02

START: ZN TYPE

 

 

NO RESPONSE

00

 

A zone list is a set of zones that can be used to initiate the start or stop relay action. If a zone list is being used to start this relay action, enter the zone list number, 1-4. If a zone list is not being used, enter 0. Press [] to continue.

A Zone Type/System Operation can be used instead of or in addition to an Event/Zone List combination or a specific zone to start the relay action. If a Zone Type/System Operation is being used, enter the 2-digit code as listed in the table that follows.

Press [] to continue.

Choices for Start/Stop Zone Types and System Operations:

00

= No Response (Not Used)

 

23

= No Alarm Response

01

= Entry/Exit #1

31

= End of Exit Time

02

= Entry/exit #2

32

= Start of Entry Time

03

= Perimeter

33

= Any Burglary Alarm

04

= Interior Follower

34

= Code + [#] + 71 Key Entry

05

= Trouble Day/Alarm Night

35

= Code + [#] + 72 Key Entry

06

= 24-Hr. Silent

 

 

= At Bell Timeout **

36

07

= 24-Hr. Audible

37

= 2 Times Bell Timeout **

08

= 24-Hr. Auxiliary

38

= Chime

09

= Fire Alarm or Trouble

39

= Fire Alarm

10

= Interior w/Delay

40

= Bypassing

20

= Arming-STAY

31

= End of Exit Time

21

= Arming-AWAY

41

= AC Power Fail

22

= Disarming (Code + Off)

 

42

= System Battery Low

*Stop condition only

**Or at disarming, whichever occurs earlier

43 = Communication failure

44 = RF Low Battery

45 = Polling Loop Failure

51 = RF Receiver Failure

52 = Kissoff

54 = Fire Zone Reset

55 = Disarm + 1 Minute

56 = XX Minutes (enter XX in field 1*74) * 57 = YY Seconds (enter YY in field 1*75) * 58 = Duress

60 = Audio Alarm Verification (must be selected for both START and STOP operation)

If you are using options 56 and/or 57 (usually as the STOP Zone Type), you must program data fields 1*74 and 1*75 for the respective relay timeouts for minutes and seconds.