Honeywell 2-Partitioned Security System, VISTA-40 manual Relay Voice Descriptors, Promptexplanation

Models: 2-Partitioned Security System VISTA-40

1 36
Download 36 pages 10.09 Kb
Page 25
Image 25
Relay Voice Descriptors

PROMPTEXPLANATION

01 ADD ZONE #

00=QUIT00

 

01

Del Zn LIST ?

 

 

1=YES

0=NO

0

 

 

 

 

 

 

 

 

 

 

01

DEL ZONES ?

 

 

1=YES

0=NO

0

 

 

 

 

 

 

 

 

 

 

 

01 Zn to DELETE ?

00=QUIT00

VIEW Zn LIST ?

00=QUIT00

01ASSIGNED ZONE

00=QUIT00

Using 2-digit entries, enter each zone to be included in this zone list. Press [] after you enter each zone number.

When you have entered all zones, enter 00.

Press [] to continue.

Enter 0 to save this zone list. Enter 1 to delete it.

Enter 1 to delete one or more zones in that zone list. Enter 0 if no changes are necessary. If you enter 1, the following screen appears; otherwise, the "Enter Zone LIST" prompt reappears.

Enter each zone number to be deleted from the zone list, pressing [] after each number.

This display appears if you pressed 00 at the “Enter Zone LIST” prompt. Enter the zone list number that you wish to view.

Press [] to continue.

Press [] to scroll through all zones in that list. Enter 00 +[] to quit.

Press 1 to exit Menu Mode.

Press []99 to exit Program Mode.

Relay Voice Descriptors

If you are using the 4285/4286 VIP Module, you can program voice descriptors for each relay output. The descriptors are announced by the voice module when you access the relays via the # 70 Relay Access Mode over the telephone.

Each voice descriptor can consist of up to 3 words selected from the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list (later in this section).

The index numbers from this vocabulary list are to be used for relay voice descriptors only. For normal system voice annunciation (e.g., alarms, troubles, status), use the highlighted words in the alpha vocabulary list in the Alpha Programming part of this guide.

To enter relay voice descriptors, do the following:

1.From Data Field Programming mode, press #93 to display the "ZONE PROG?" prompt.

2.Press 0 (NO) to each menu option until the "RLY VOICE DESCR?" prompt is displayed. Follow the instructions below. While in this mode, press [] to advance to next screen. Press [#] to back up to previous screen.

PROMPTEXPLANATION

RLY VOICE DESCR?

 

1=YES 0=NO

0

ENTER RELAY NO.

00=QUIT 01

01 ENTER DESC d1

01 ENTER DESC d2

01 ENTER DESC d3

Press 1 to program voice descriptors for relays.

Enter the 2-digit relay number (01-08) for the relay desired, or enter 00 to quit Relay Voice Descriptor Programming Mode.

Press []

From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index number for the first word of the relay descriptor phrase.

Press [] to accept entry.

From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index number for the second word of the relay descriptor phrase. If second word is not desired, press 000. Press [] to accept entry.

From the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list, enter the 3-digit index number for the third word of the relay descriptor phrase. If third word is not desired, press 000.

Press [] to accept entry. The “ENTER RELAY NO.” prompt appears. Enter the next relay number to be programmed. When you have programmed all relay devices, enter 00 to quit.

Enter []99 to exit Program Mode.

– 25 –

Page 25
Image 25
Honeywell 2-Partitioned Security System, VISTA-40 manual Relay Voice Descriptors, Promptexplanation