Honeywell 2-Partitioned Security System manual Device Programming, Promptexplanation, Alpha Keypad

Models: 2-Partitioned Security System VISTA-40

1 36
Download 36 pages 10.09 Kb
Page 21
Image 21
Device Programming

Device Programming

This menu is used to program keypads, receivers, and relay modules, etc.

Device Address 00 is always set as an alpha keypad assigned to Partition 1 with no sounder suppression options, and these settings cannot be changed.

From Data Field Programming mode, press [#]93 to display "ZONE PROG?" Press 0 repeatedly to display "DEVICE PROG?"

PROMPTEXPLANATION

 

DEVICE PROG?

 

 

1=YES 0=NO

0

 

 

 

 

 

 

 

 

DEVICE ADDRESS

 

 

01-15, 00=QUIT

01

 

 

 

 

 

 

 

DEVICE TYPE

0

Press 1 to enter Device Programming.

The device address identifies the device to the control. Enter the 2-digit device address number to match the device’s physical address setting (01-15).

NOTE: If using the 4285/4286 Voice Module, it must be used at Device Address 04.

Select the type of addressable device as follows:

0

= device not used

3

= RF receiver (5881)

1

= alpha keypad (6139/6160)

4

= output relay module (4204)

2

= fixed keypad (6137/6150)

5

= voice (VIP) Module (4285/4286)

Press [] to accept entry.

Alpha Keypad

PROMPTEXPLANATION

01 CONSOLE PART.

1

01 SOUND OPTION

00

If you selected device type 1 (alpha keypad) or 2 (fixed keypad), this prompt appears. Enter the addressable device’s default partition number (1 to maximum number of partitions programmed for system in field 2*00). This is the primary partition for the device.

Press [] to accept entry.

Keypads can be individually programmed to suppress arm/disarm beeps, entry/exit beeps and chime mode beeps. This helps prevent unwanted sounds from disturbing users in other areas of the premises.

Enter a number 00-03for the keypad sounding suppression options desired for the keypad as follows: 00 = no suppression

01 = suppress arm/disarm & entry/exit beeps

02 = suppress chime mode beeps only

03 = suppress arm/disarm, entry/exit and chime mode beeps Press [] to accept entry.

RF Expander

PROMPTEXPLANATION

01 RF EXPANDER

 

HOUSE ID

00

If you selected device type 3 (RF receiver), this prompt appears. Enter the 2-digit House ID (00-31). This is required if you are using a wireless keypad (5827/5827BD).

Press [] to accept entry.

VIP Module

PROMPTEXPLANATION

01 MODULE PART.

1

If you selected device type 5 (VIP Module), this prompt appears. Enter the partition number 1-2in which the module is located.

Press [] to accept entry.

Press 00 + [] to exit Menu mode. Press 99 to exit Program mode.

– 21 –

Page 21
Image 21
Honeywell 2-Partitioned Security System manual Device Programming, Promptexplanation, Alpha Keypad, RF Expander, VIP Module