Metric | Affected objects | Description |
|
|
|
|
| greater the possibility that the equipment experiences |
|
| temperatures above the maximum allowable temperature, as |
|
| determined by ASHRAE. |
|
|
|
Rack Cooling IndexLO® | Data center racks | RCILOTM/SM is the complement to RCIHITM/SM to draw attention to |
| Zone racks | the supply air that is below the minimum recommended |
|
| temperature, as determined by ASHRAE. |
|
|
|
RCIHI®/RCILO® Inlet | Data center racks | The number of racks that have RCIHITM/SM or RCILOTM/SM |
Measurement Count | Zone racks | measurements |
|
|
|
Average Rack Inlet | Zone racks | The average of the top, middle, and bottom rack inlet |
Temperature |
| temperature sensors on each rack for each zone |
|
|
|
Average Rack | Zone racks | The average of the top, middle, and bottom rack discharge |
Discharge |
| temperature sensors on each rack for each zone |
Temperature |
|
|
|
|
|
Min, Max, Average | Data center racks | Dew point calculated at the top inlet on each rack for each |
Rack Top Inlet Dew | Zone racks | zone |
Point |
|
|
|
|
|
Min, Max, Average | Data center racks | Rack top inlet temperature degrees change per hour, for each |
Rack Cold Top Inlet | Zone racks | zone |
Air Temp Rate of |
|
|
Change |
|
|
|
|
|
Min, Max, Average | CRAH/CRAC | Supply temperatures calculated for each zone |
CRAC supply | Zone |
|
temperature |
|
|
|
|
|
Min, Max, Average | CRAH/CRAC | Return temperatures calculated for each zone |
CRAC return | Zone |
|
temperature |
|
|
|
|
|
Min, Max, Average | CRAH/CRAC | Dew point temperatures for supply air for each zone |
CRAC supply dew | Zone |
|
point temperature |
|
|
Min, Max, Average | CRAH/CRAC | Dew point temperatures for return air for each zone |
CRAC return dew | Zone |
|
point temperature |
|
|
Custom Metrics tab
The Custom Metrics tab only appears at the data center level, if you have defined and configured custom calculation inspectors in the HP Insight Environmental Configurator. For more information, see the HP Insight Environmental Configurator User Guide.
The Custom Metrics tab displays:
•All data inspectors configured for the data center
•Historical data for the monitored calculation groups
Accessing the Custom Metrics tab
1.From the Navigation panel, select the data center you want to display.
Views 38