Metric

Affected objects

Description

 

 

 

 

 

greater the possibility that the equipment experiences

 

 

temperatures above the maximum allowable temperature, as

 

 

determined by ASHRAE.

 

 

 

Rack Cooling IndexLO®

Data center racks

RCILOTM/SM is the complement to RCIHITM/SM to draw attention to

 

Zone racks

the supply air that is below the minimum recommended

 

 

temperature, as determined by ASHRAE.

 

 

 

RCIHI®/RCILO® Inlet

Data center racks

The number of racks that have RCIHITM/SM or RCILOTM/SM

Measurement Count

Zone racks

measurements

 

 

 

Average Rack Inlet

Zone racks

The average of the top, middle, and bottom rack inlet

Temperature

 

temperature sensors on each rack for each zone

 

 

 

Average Rack

Zone racks

The average of the top, middle, and bottom rack discharge

Discharge

 

temperature sensors on each rack for each zone

Temperature

 

 

 

 

 

Min, Max, Average

Data center racks

Dew point calculated at the top inlet on each rack for each

Rack Top Inlet Dew

Zone racks

zone

Point

 

 

 

 

 

Min, Max, Average

Data center racks

Rack top inlet temperature degrees change per hour, for each

Rack Cold Top Inlet

Zone racks

zone

Air Temp Rate of

 

 

Change

 

 

 

 

 

Min, Max, Average

CRAH/CRAC

Supply temperatures calculated for each zone

CRAC supply

Zone

 

temperature

 

 

 

 

 

Min, Max, Average

CRAH/CRAC

Return temperatures calculated for each zone

CRAC return

Zone

 

temperature

 

 

 

 

 

Min, Max, Average

CRAH/CRAC

Dew point temperatures for supply air for each zone

CRAC supply dew

Zone

 

point temperature

 

 

Min, Max, Average

CRAH/CRAC

Dew point temperatures for return air for each zone

CRAC return dew

Zone

 

point temperature

 

 

Custom Metrics tab

The Custom Metrics tab only appears at the data center level, if you have defined and configured custom calculation inspectors in the HP Insight Environmental Configurator. For more information, see the HP Insight Environmental Configurator User Guide.

The Custom Metrics tab displays:

All data inspectors configured for the data center

Historical data for the monitored calculation groups

Accessing the Custom Metrics tab

1.From the Navigation panel, select the data center you want to display.

Views 38