Lennox International Inc Dave Lennox Signature Collection XC17 Air Conditioner, 506510-01 Airflow

Models: Dave Lennox Signature Collection XC17 Air Conditioner 506510-01

1 49
Download 49 pages 11.15 Kb
Page 27
Image 27
AIRFLOW

ADDING OR REMOVING REFRIGERANT

This system uses HFC−410A refrigerant which operates at much higher pressures than HCFC−22. The pre−installed liquid line filter drier is approved for use with HFC−410A only. Do not replace it with components designed for use with HCFC−22. This unit is NOT approved for use with coils which use capillary tubes or fixed orifices as a refrigerant metering device.

Check airflow using the Delta−T (DT) process using the illustration in Figure 12.

AIRFLOW

 

 

INDOOR COIL

Dry−bulb

DT

Temperature of air

80 24 24 24 23 23 22 22 22 20 19 18 17 16 15

 

entering indoor

 

78 23 23 23 22 22 21 21 20 19 18 17 16 15 14

coil ºF

 

76 22 22 22 21 21 20 19 19 18 17 16 15 14 13

 

 

 

 

74 21 21 21 20 19 19 18 17 16 16 15 14 13 12

A

 

72 20 20 19 18 17 17 16 15 15 14 13 12 11 10

 

 

70 19 19 18 18 17 17 16 15 15 14 13 12 11 10

Wet−bulb ºF 57 58 59 60 61 62 63 64 65 66 67 68 69 70

DRY

 

B

BULB

 

 

CManual backgroundManual background TDrop

53º

19º

air flow

air flow

A

72º

B

64º

INDOOR COIL

All temperatures are expressed in ºF

DRY BULB

WET BULB

Use the following procedure to adjust for optimal air flow across the indoor coil:

 

1.

Determine the desired DT

A) and wet bulb (B). DT

 

is the intersecting value of A and B in the table (see triangle).

 

2.

Find temperature drop across coil

 

 

(A and C). Temperature Drop Formula: (TDrop) = A minus C.

 

3.

Determine if fan needs adjustment ference between the measured

TDrop and the desired

 

DT (TDropDT) is within +3º, no adjustment is needed. See example below:

 

Assume DT = 15 and A temp. = 72º, these C temperatures would necessitate stated actions:

TDrop

DT

=

ºF

ACTION

 

53º

19

15

=

4

Increase the airflow

Changing air flow affects all temperatures; recheck

 

 

 

 

=

 

 

temperatures to confirm that the temperature drop

58º

14

15

−1

(within +3º range) no change and DT are within +3º.

62º

10

15

=

−5

Decrease the airflow

 

4.Adjust the fan speed

Figure 12. Checking Indoor Airflow over Evaporator Coil using Delta−T Chart

Page 27

XC17 SERIES

Page 27
Image 27
Lennox International Inc Dave Lennox Signature Collection XC17 Air Conditioner, 506510-01 installation instructions Airflow