LED CODES AND SEQUENCE OF OPERATIONS

LED CODES AND SEQUENCE OF OPERATIONS

During start up, the LED will first display any error conditions (see table 12) if present. If no errors are detected then the LED code indicating one or two stage operation will display then a long pause. The RPM indicator is displayed next. After the RPM indicator is displayed there is a short pause and the sequence repeats if a thermostat demand is still present. See Figure 22 for LED sequence of operations. See table 13 for description of flash and pause durations.

Table 12. Error/Fault LED Codes

Unit Status

Motor Control LED

Possible Cause

 

 

 

Mismatched RPM

Fast Flash with no pause

Internal feedback, PWM does not match tar-

get.

 

 

 

 

 

CRC Failure

Constant ON.

Microcontroller CRC failure.

 

 

 

Table 13. Fan Motor Board Unit LED Codes

Unit Status

Unit Status

Motor Control LED

 

 

 

One Stage Operation

Low Stage Y

One slow flash, then short pause.

 

 

 

RPM Indicator

 

 

NOTE There is a long pause between stage

RPM Indicator

Appropriate number of flashes (See Tables

operation and RPM indicator. See Tables 1 and 2

11 and 2).

 

 

 

for LED RPM indicator.

 

 

 

 

 

Flash Flash = Three flashes per second.

 

 

Slow Flash = One flash per second.

 

 

Short Pause = Two seconds of OFF time.

 

 

Long Pause = Five seconds of OFF time.

 

 

 

 

 

DEMAND BEGINS

FAN MOTOR PWM CONTROL (ONE STAGE AND SINGLE FAN SPEED)

MISMATCHED

RPM

CRC FAILURE

DEFAULT FAN MOTOR SPEED

USED

DEFAULT FAN MOTOR SPEED USED

LED CONTINUOUS FAST

FLASH

LED CONSTANT ON

REPLACE FAN MOTOR CONTROL BOARD

REPLACE FAN MOTOR CONTROL BOARD

YES

SINGLE STAGE

OR EDA

OPERATION

NO

DEMAND

ENDED

ECM1/Y1

ONLY OR ECM2/Y2

ONLY

FAN MOTOR RPM SET PER JUMPER SETTINGS

STAGE LED INDICATOR: ONE Manual backgroundManual backgroundSLOW FLASH AND ONE SHORT PAUSE FOR SINGLE STAGE OR EDA OPERATION

LED RPM INDICATOR:

EXAMPLE: (2−TON

UNIT) – 5 SLOW

FLASHES AND ONE

LONG PAUSE

Figure 22. Single Stage LED Sequence of Operation

Page 43

XC17 SERIES

Page 43
Image 43