3ROUTE CONTROL WIRES

Install low voltage control wiring from outdoor to indoor unit and from thermostat to indoor unit as illustrated. See Figures 10 and 10 for typical configurations.

ARun 24VAC control wires through hole with grommet.

B Make 24VAC control wire connections to Main Control.

NOTE AC control wires inside control panel.

NOTE

 

 

 

 

B

separation of field installed low and high voltage circuits.

NOTE For proper voltages, select thermostat wire (control wires)

gauge per table below.

 

 

 

 

 

 

 

 

 

 

 

 

MAIN CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WIRE RUN LENGTH

AWG# INSULATION TYPE

 

 

 

 

 

 

LESS THAN 100’ (30 METERS)

18

TEMPERATURE RATING

 

 

 

 

 

MORE THAN 100’ (30 METERS)

16

35ºC MINIMUM.

 

 

 

 

 

 

 

 

 

 

 

CONTROL PANEL

HOLE A

4ROUTE HIGH VOLTAGE AND GROUND WIRES

Any excess high voltage field wiring should be trimmed and secured away from any low voltage field wiring. To facilitate a conduit, a cutout is located in the bottom of the control panel. Connect conduit to the control panel using a proper conduit fitting.

PIPING PANEL

HIGH VOLTAGE

CONDUIT HOLE

WATERTIGHT

CONDUIT

FITTING

WATERTIGHT

FLEXIBLE

CONDUIT

TO SERVICE

DISCONNECT BOX

CONTROL PANEL

GROUND LUG

CONTACTOR

ELECTRICAL INLET (HIGH VOLTAGE)

WIRING ENTRY POINTS

ELECTRICAL INLET (CONTROL WIRING TAGE).

USE BUSHING PROVIDED IN BAG ASSEMBLY HERE.

ACCESS VIEW

Page 20

506510−01

Page 20
Image 20
Lennox International Inc 506510-01 installation instructions 3ROUTE Control Wires, 4ROUTE High Voltage and Ground Wires