Outdoor Main

 

 

 

 

 

Control LEDs

 

Possible

 

 

 

 

 

 

Condition

Solution

Clearing Status

 

 

 

Cause(s)

DS15

 

DS13

 

 

 

 

 

 

 

 

 

 

 

Yellow

 

Red

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Outdoor unit power disconnect is open.

 

 

 

 

 

 

2

Unit circuit breaker or fuse(s) is open.

 

 

 

 

 

 

3

Unit contactor has failed to close.

 

 

 

 

 

 

 

S Check compressor contactor wiring and con-

 

 

 

 

 

 

 

nectors

 

 

 

 

 

 

 

S Check for compressor contactor failure (burned,

 

 

 

 

 

 

 

pitted or open)

 

 

 

 

 

Compressor has

 

S Check wiring and connectors between supply and

 

 

 

 

 

an open circuit

 

 

5 Flashes

 

 

 

 

compressor

Clears after one normal

 

 

 

due to power dis-

 

then

 

OFF

Open Circuit

 

S Check for low pilot voltage at compressor con-

compressor run cycle or

 

connection, fuse

 

Pause

 

 

 

 

tactor coil

power reset.

 

 

 

is open or other

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

similar conditions.

High pressure switch is open and requires manual

 

 

 

 

 

 

 

reset.

 

 

 

 

 

 

5

Open circuit in compressor supply wiring or con-

 

 

 

 

 

 

 

nections.

 

 

 

 

 

 

6

Unusually long compressor protector reset time due

 

 

 

 

 

 

 

to extreme ambient temperature.

 

 

 

 

 

 

7

Compressor windings are damaged.

 

 

 

 

 

 

 

S Check compressor motor winding resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Run capacitor has failed.

 

 

 

 

 

 

2

Open circuit in compressor start wiring or connec-

Clears when amperage is

6 Flashes

 

 

 

Current not

 

tions.

 

 

Open Start

 

detected in RUN and

 

 

 

 

then

 

OFF

sensed by Start

 

S Check wiring and connectors between supply and

 

Circuit

 

START sensors, or after

Pause

 

 

 

transformer.

 

the compressor S terminal

power reset.

 

 

 

 

 

3

Compressor start winding is damaged.

 

 

 

 

 

 

 

 

 

 

 

 

S Check compressor motor winding resistance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Open circuit in compressor start wiring or connections.

 

7 Flashes

 

 

Open Run

Current not

 

S Check wiring and connectors between supply and

Clears when amperage is

then

 

OFF

sensed by run

 

the compressor R terminal

detected in RUN and

 

Circuit

 

START sensors, or after

Pause

 

 

transformer.

2

Compressor start winding is damaged.

 

 

 

power reset.

 

 

 

 

 

 

 

 

 

 

 

 

 

S Check compressor motor winding resistance

 

 

 

 

 

 

 

 

 

8 Flashes

 

OFF

Welded

Compressor

1

Compressor contactor failed to open.

Clears after one normal

then

 

Contactor

always runs

2

Thermostat demand signal not connected to module.

compressor run cycle or

Pause

 

 

after power reset.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9 Flashes

 

 

 

 

1

Control circuit transformer is overloaded.

Clears after voltage is higher

 

 

 

 

 

 

 

 

Secondary

24VAC is below

2

Low line voltage (contact utility if voltage at disconnect

than 20VAC for two

then

 

OFF

 

Low Voltage

18VAC.

 

is low).

seconds, or after power

Pause

 

 

 

 

 

 

 

 

S Check wiring connections

reset.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fast simultaneous

 

 

 

 

 

flashing of DS11,

OEM Mode

Factory Test Mode.

 

 

 

DS13, DS14 and

 

 

 

 

 

DS15

 

 

 

 

 

 

 

 

 

 

 

 

 

 