Outdoor Main Control |
|
|
|
| ||
LEDs |
|
|
|
| ||
|
| Condition | Possible Cause(s) |
| Solution | |
DS11 | DS14 Red |
| ||||
|
|
|
| |||
Green |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
| 1 Fast | Heating Low |
|
|
| |
OFF | Flash then |
|
|
| ||
Capacity |
|
|
| |||
| Pause |
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
| 2 Fast | Heating High |
|
|
| |
OFF | Flash then |
|
|
| ||
Capacity |
|
|
| |||
| Pause |
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
| 2 Fast |
|
|
|
| |
ON | Flash then | Defrost |
|
|
| |
| Pause |
| These are codes that show status of operation whether in low stage or high stage, heating or cooling, | |||
|
|
| ||||
1 Fast |
| Cooling Low | defrost or in the EDA mode. |
|
| |
|
|
|
| |||
Flash then | OFF |
|
|
| ||
Capacity |
|
|
| |||
Pause |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
2 Fast |
| Cooling High |
|
|
| |
Flash then | OFF |
|
|
| ||
Capacity |
|
|
| |||
Pause |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
|
| |
2 Fast |
| Dehumidification |
|
|
| |
Flash then | ON |
|
|
| ||
Mode |
|
|
| |||
Pause |
|
|
|
| ||
|
|
|
|
| ||
|
|
|
|
| ||
|
|
| ALERT STATUS | |||
|
|
|
|
|
| |
OFF | SLOW | Low Pressure | 1 Restricted air flow over |
|
| |
Flash | Fault | indoor or outdoor coil. |
|
| ||
| 1 Remove any blockages or restrictions from coils and/or fans. Check | |||||
|
|
| ||||
|
|
| 2 Improper refrigerant | |||
|
| Low Pressure |
| indoor and outdoor fan motor for proper current draws. | ||
OFF | ON | charge in system. |
| |||
|
| |||||
Switch Lockout | 2 Check system charge using approach and subcooling temperatures. | |||||
|
| 3 Improper metering de- | ||||
|
|
| 3 | Check system operating pressures and compare to unit charging | ||
SLOW |
| High Pressure | vice installed or incorrect | |||
OFF |
| charts. | ||||
operation of metering de- |
| |||||
Flash | Fault |
| ||||
4 | Make sure all pressure switches and sensors have secure connec- | |||||
| vice. | |||||
|
|
| ||||
|
|
|
| tions to system to prevent refrigerant leaks or errors in pressure and | ||
|
| High Pressure | 4 Incorrect or improper |
| ||
|
|
| temperature measurements. | |||
ON | OFF | Discharge Sensor | sensor location or con- |
| ||
|
| |||||
|
| Lockout | nection to system. |
|
| |
|
|
|
|
|
| |
SLOW | ON | Discharge Line | This code detects high discharge temperatures. If the discharge line temperature exceeds a temperature | |||
Flash | Temperature Fault | |||||
|
|
| of 279ºF (137ºC) during compressor operation, the control will de−energize the compressor contactor | |||
|
| Discharge Line | output (and the defrost output if active). The compressor will remain off until the discharge temperature | |||
FAST |
| has dropped below 225ºF (107ºC). See Figure 21 for further details concerning lockouts and reset | ||||
ON | Temperature | |||||
Flash | procedures. |
|
| |||
| Lockout |
|
| |||
|
|
|
|
| ||
|
|
|
| |||
OFF | Fast Flash | Discharge Sensor | The control detects open or short sensor or out of temperature sensor range. This fault is detected by | |||
Fault | allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is | |||||
|
| not within range after 90 seconds, the control will raise the alarm. | ||||
|
|
| ||||
|
|
|
|
|
| |
Fast simultaneous | OEM Mode | Factory Test Mode. |
|
| ||
flashing of DS11, DS13, |
|
| ||||
|
|
|
| |||
DS14 and DS15 |
|
|
|
| ||
|
|
|
|
|
|