Troubleshooting

13.0TROUBLESHOOTING

The information below indicates various symptoms a user may encounter in the event the UPStation GXT2-6000RT208 develops a problem. Use this information to determine whether external factors caused the problem and how to remedy the situation.

1.The Fault indicator will illuminate, indicating the UPS has detected a problem.

2.An alarm will sound, alerting that the UPS requires attention.

3.One or more additional Load Level/Battery Level indicators will be illuminated to provide a diagnostic aid to the operator, as described below:

A B C

AC Input indicator

DE

Fault indicator

Battery indicators

Load Level indicators

Bypass indicator

Battery indicator UPS ON indicator

Table 4

Fault indicators

 

 

Indicator status

Diagnosis/Audible alarm

 

 

All indicators

On bypass due to output overload; beep every half-second

Indicator A

 

On bypass due to overtemperature condition on L1; 1-second beep every 4 seconds

 

On bypass due to overtemperature condition on L2; 2-second beep every 4 seconds

 

 

Indicator B

 

On bypass due to DC bus overvoltage on L1; 1-second beep every 4 seconds

 

On bypass due to DC bus overvoltage on L2; 2-second beep every 4 seconds

 

 

Indicator C

 

On bypass due to control power supply failure on L1; 1-second beep every 4 seconds

 

On bypass due to control power supply failure on L2; 2-second beep every 4 seconds

 

 

Indicator D

 

On bypass due to PFC failure on L1; 1-second beep every 4 seconds

 

On bypass due to PFC failure on L2; 2-second beep every 4 seconds

 

 

Indicator E

 

On bypass due to inverter failure on L1; 1-second beep every 4 seconds

 

On bypass due to inverter failure on L2; 2-second beep every 4 seconds

 

 

Indicators A&B

Inverter-to-Inverter communications failure; half-second beep every 1 second

Indicators A&C

UPS failed battery test; 2-second beep every 60 seconds

Indicators A&D

L1 to L2 phase angle unacceptable

Indicators B&C

REPO is currently activated, UPS output cannot be started by any method

 

 

UPS is OFF due to previous REPO (REPO is no longer activated). Once utility power is

Indicators B&D

restored, press the OFF button twice within four seconds (to clear the alarm), then press the

 

 

ON button to start UPS (Auto-restart is NOT possible).

Indicators C&E

UPS shutdown due to command from communications (RS232 or SNMP); no beep

Indicators D&E

UPS is OFF due to charger overvoltage; 1-second beep every 4 seconds

AC Input indicator On &

AC input has been applied to start UPS but the batteries are either missing or below the

Battery indicator Flashing

minimal level to allow the UPS to start; continuous audible alarm

Bypass indicator Flashing

Bypass voltage is present, but is disabled for use because the voltage or frequency is outside

acceptable limits

 

 

Under fault conditions, the Fault indicators will be illuminated indefinitely while the battery charger is operational, or for a maximum of 5 minutes while the battery charger is not operational.

If a problem persists, consult your local dealer, Liebert representative or contact the Liebert World- wide Support Group. Please have the UPS model number and serial number available at the time of your inquiry.

36

Page 42
Image 42
Liebert GXT2-6000 RT208 user manual Troubleshooting, Fault indicators, Indicator status Diagnosis/Audible alarm