Specifications

14.0SPECIFICATIONS

Table 8

UPS specifications

 

 

 

 

 

Model Number

GXT2-6000RT208

 

 

4200W/5200VA at 127/220 (120 or 240 degrees only)

 

 

4200W/5200VA at 120/208 (120 or 240 degrees)

 

Model Rating

4200W/6000VA at 120/240 (180 degrees)

 

4200W/6000VA at 115/230 (180 degrees only)

 

 

 

 

3780W/5400VA at 110/220 (180 degrees only)

 

 

3360W/4800VA at 100/200 (180 degrees only)

DIMENSIONS in (mm)

 

 

Unit W x D x H in. (mm)

6.9 x 24.2 x 16.9 (176 x 615 x 430)

 

Shipping W x D x H in. (mm)

13.2 x 27.8 x 20.9 (335 x 705 x 530)

WEIGHT lbs (kg)

 

 

Unit

67 (30.3)

 

Shipping

76.3 (34.6)

INPUT AC PARAMETERS

 

 

Nominal Operating Frequency

50 or 60 Hz (Factory Default = 60)

 

Factory Default VAC

120/208 VAC at 120 degrees

L1-L2 Factory Default Input Phase

120 degrees

 

Angle

 

 

 

Allowable Input Phase Angle

120, 180, 240 degrees, Auto-sensing on application of AC

 

(Restrictions for L-N voltages other than 120 VAC)

 

 

Factory Default L1-N, L2-N VAC

120 VAC nominal

User Configurable L1-N, L2-N VAC

100/110/115/120/127 VAC (May be modified using configuration program)

L1-N, L2-N, Operating Voltage Range

Without Battery Operation (Except 100 VAC L-N Operation)

 

100% - 90% loading

90 VAC - 140 VAC

 

90% - 70% loading

80 VAC - 140 VAC

 

70% - 30% loading

70 VAC - 140 VAC

 

30% - 0% loading

60 VAC - 140 VAC

L1-N, L2-N, Operating Voltage Range

Without Battery Operation (100 VAC L-N Operation)

 

100% - 70% loading

80 VAC - 140 VAC

 

70% - 30% loading

70 VAC - 140 VAC

 

30% - 0% loading

60 VAC - 140 VAC

L1-N, L2-N Max. Allowable VAC

150 VAC

 

Input Frequency w/o Battery

40 - 70 Hz

 

Operation

 

 

Input Power Connection

See Distribution Box Options

OUTPUT AC PARAMETERS

 

 

Factory Default VAC

120/208 VAC @ 120 degrees

 

L1-L2 Factory Default

120 degrees

 

Output Phase Angle

 

 

 

Allowable Output Phase Angle

120, 180, 240 degrees Auto-sensing on initial application of input AC

Factory Default L1-N, L2-N VAC

120 VAC nominal

User Configurable L1-N, L2-N VAC

100/110/115/120/127 VAC, ±3%

 

Output Connections

See Distribution Box Options

 

Frequency

50 Hz or 60 Hz, Nominal

 

Waveform

Sinewave

 

Main Mode Overload

200% for 8 cycles; 130% for 10 seconds with transfer to bypass

Bypass Protection Limits

 

 

Disable Bypass operation

If input voltage exceeds ±15% of the nominal voltage

 

Re-enable Bypass operation

If input voltage returns to within ±10% of nominal output voltage

 

Disable Bypass operation

When the input frequency prevents synchronous operation

41

Page 47
Image 47
Liebert GXT2-6000 RT208 user manual Specifications, UPS specifications