Specifications
41
14.0 SPECIFICATIONS

Table 8 UPS specifications

Model Number GXT2-6000RT208
Model Rating
4200W/5200VA at 127/220 (120 or 240 degrees only)
4200W/5200VA at 120/208 (120 or 240 degrees)
4200W/6000VA at 120/240 (180 degrees)
4200W/6000VA at 115/230 (180 degrees only)
3780W/5400VA at 110/220 (180 degrees only)
3360W/4800VA at 100/200 (180 degrees only)
DIMENSIONS in (mm)
Unit W x D x H in. (mm) 6.9 x 24.2 x 16.9 (176 x 615 x 430)
Shipping W x D x H in. (mm) 13.2 x 27.8 x 20.9 (335 x 705 x 530)
WEIGHT lbs (kg)
Unit 67 (30.3)
Shipping 76.3 (34.6)
INPUT AC PARAMETERS
Nominal Operating Frequency 50 or 60 Hz (Factory Default = 60)
Factory Default VAC 120/208 VAC at 120 degrees
L1-L2 Factory Default Input Phase
Angle 120 degrees
Allowable Input Phase Angle 120, 180, 240 degrees, Auto-sensing on application of AC
(Restrictions for L-N voltages other than 120 VAC)
Factory Default L1-N, L2-N VAC 120 VAC nominal
User Configurable L1-N, L2-N VAC 100/110/115/120/127 VAC (May be modified using configuration program)
L1-N, L2-N, Operating Voltage Range Without Battery Operation (Except 100 VAC L-N Operation)
100% - 90% loading 90 VAC - 140 VAC
90% - 70% loading 80 VAC - 140 VAC
70% - 30% loading 70 VAC - 140 VAC
30% - 0% loading 60 VAC - 140 VAC
L1-N, L2-N, Operating Voltage Range Without Battery Operation (100 VAC L-N Operation)
100% - 70% loading 80 VAC - 140 VAC
70% - 30% loading 70 VAC - 140 VAC
30% - 0% loading 60 VAC - 140 VAC
L1-N, L2-N Max. Allowable VAC 150 VAC
Input Frequency w/o Battery
Operation
40 - 70 Hz
Input Power Connection See Distribution Box Options
OUTPUT AC PARAMETERS
Factory Default VAC 120/208 VAC @ 120 degrees
L1-L2 Factory Default
Output Phase Angle 120 degrees
Allowable Output Phase Angle 120, 180, 240 degrees Auto-sensing on initial application of input AC
Factory Default L1-N, L2-N VAC 120 VAC nominal
User Configurable L1-N, L2-N VAC 100/110/115/120/127 VAC, ±3%
Output Connections See Distribution Box Options
Frequency 50 Hz or 60 Hz, Nominal
Waveform Sinewave
Main Mode Overload 200% for 8 cycles; 130% for 10 seconds with transfer to bypass
Bypass Protection Limits
Disable Bypass operation If input voltage exceeds ±15% of the nominal voltage
Re-enable Bypass operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation When the input frequency prevents synchronous operation