Troubleshooting

Using the configuration program, the user may specify the number of GXT2-144VBATT external bat- tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.

Table 7 shows estimated run times at different loads.

Table 7

Battery run times

 

 

 

 

 

 

 

 

 

6000VA Run Time

Battery/External Cabinets

Load%

in Minutes

 

 

10%

75

 

 

20%

38

 

 

30%

25

 

 

40%

18

 

Internal Battery

50%

14

 

60%

11

 

 

 

 

70%

9

 

 

80%

7

 

 

90%

6

 

 

100%

5

 

 

10%

156

 

 

20%

90

 

 

30%

62

 

 

40%

44

Internal Battery + 1 External

50%

34

 

Battery Cabinet

60%

28

 

 

70%

23

 

 

80%

19

 

 

90%

16

 

 

100%

14

 

 

10%

235

 

 

20%

137

 

 

30%

99

 

 

40%

74

Internal Battery + 2 External

50%

58

 

Battery Cabinets

60%

47

 

 

70%

39

 

 

80%

33

 

 

90%

28

 

 

100%

25

 

 

10%

313

 

 

20%

183

 

 

30%

133

 

 

40%

103

Internal Battery + 3 External

50%

82

 

Battery Cabinets

60%

67

 

 

70%

55

 

 

80%

47

 

 

90%

41

 

 

100%

36

 

 

10%

391

 

 

20%

229

 

 

30%

166

 

 

40%

129

Internal Battery + 4 External

50%

105

 

Battery Cabinets

60%

87

 

 

70%

73

 

 

80%

63

 

 

90%

54

 

 

100%

47

39