Configuration Program
8.5.4Frequency Selection
The UPS is normally designed for 50Hz or 60Hz operation. The factory default corresponds to the model. All models are capable of being used as 50Hz or 60Hz systems. The UPS will automatically sense the utility frequency when first plugged in and set the nominal frequency to match. Therefore, for all normal use the Auto Sense button should be selected.
Some special applications require that the UPS be used as a frequency converter. Frequency con- verter 50Hz or frequency converter 60Hz may be selected.
Note that frequency converter operation disables the Bypass. If, for any reason, the UPS inverter is unable to power the load, the alternate bypass to utility power will not be available and power will be removed from any load.
8.6Options Tab
Computer users may choose to use versatile com- puter shutdown software that communicates with the UPS via a serial communications cable. The Options tab should not be used to modify the UPS functions for such applications.
For some industrial applications and special computer applications, the UPS may be moni- tored and controlled using external voltages and relay contact signals. The Options tab expands the UPS versatility for such applications.
Refer to your UPS manual for a description of the
The Options tab allows the behavior of the Any Mode Shutdown feature to be modified.
When the program opens or the REFRESH but- ton is pressed, the UPS setting is read by the configuration program and displayed.
Factory Default Setting Illustrated - This Options tab illustration shows the available function definitions using pin 6 and the factory default settings.
! WARNING
Auto-Enable Output
Note that when this option is selected and the UPS output is disabled using Pin 6, the UPS output can turn on automatically and without warning if the Pin 6 connection is changed.
! WARNING
Pin 6 Logic
DO NOT CHANGE THIS OPTION from the factory default setting unless you are ready to install a
24