Maintenance
12.0MAINTENANCE
The UPStation
When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours every four to six months to ensure full recharge of the batteries. Failure to recharge the batteries peri- odically will permanently degrade battery capacity.
The UPStation
12.1Battery Replacement
! CAUTION
A battery can present a risk of electrical shock and high short circuit Current. The following precautions should be observed before replacing the batteries:
•Remove rings, watches and other metal objects.
•Use a Phillips (crosshead) screwdriver with insulated grips.
•Do not lay tools or other metal objects on top of the batteries.
•If the battery replacement kit is damaged in any way or shows signs of leakage, contact your local dealer or Liebert representative immediately.
•Do not dispose of batteries in a fire. The batteries may explode.
12.1.1Internal Battery Replacement Procedures
1.Gently remove the front plastic bezels cover from the UPS by pulling forward.
2.Loosen the two captive screws on the front battery door. Lay the battery door aside for reassembly.
3.Grasp the battery pack assembly and pull it out of the front of the UPS. Be prepared to support the weight of the battery as it is withdrawn.
4.Unpack the new battery assembly taking care not to destroy the packing. Compare new and old battery assemblies to make sure they are the same. If so, proceed with Step 6; otherwise STOP and contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.
5.Line up and slide in the new replacement battery pack.
6.Reattach the front battery door, tightening the two captive screws finger tight.
7.Reattach the front plastic bezels to the UPS.
UPS
Battery
Liebert
Battery Cover
!
!
!
Battery Cover
Captive Screws
Front Bezels
NOTE
These are