Product Description

Figure 9 Piping access points

To first cooling module

or bypass flow controller **

A - Return From Cooling Modules

Install replaceable filter dryer assembly in liquid supply line B.

* Orientation determined by installer.

17-1/4"

(438mm)

16-1/8"

B - Supply to Cooling Modules

(410mm)

10" (254mm)

19" (483mm)

Dimensions are approximate

and subject to change without notice.

D - Chilled Water Return

To Chilled Water Source

C - Chilled Water Supply From Chilled Water Source

*Allow 8" (204mm) clearance for filter replacement.

**To ensure ensure all refrigerant flow is filtered, install the filter dryer assembly between the discharge line of the Liebert XDP and the first bypass flow controller or the first cooling module.

Table 2

Unit piping outlet connection sizes, inches, OD Cu

 

Model

 

 

Pipe Connection Point

 

 

 

 

 

 

 

50/60 Hz

A

B

C

 

D

 

 

 

 

 

 

 

XDP160

 

2-1/8

1-1/8

2-5/8

 

2-5/8

 

 

 

 

 

 

 

DPN000767 Pg. 3, Rev. 6

6

Page 12
Image 12
Liebert XDP user manual Unit piping outlet connection sizes, inches, OD Cu, Model Pipe Connection Point 50/60 Hz