Checklist for Liebert XDP Startup

3.1.1Calculating Refrigerant Charge—Example

Using Tables 6, 7, 8 and 9, calculate the refrigerant charge of the individual sections of your Liebert XD system. Add the calculated charge amounts to determine the amount of R-134a refrigerant required for one system combining a Liebert XDP with Liebert XD cooling modules (Liebert XDCF, Liebert XDH, Liebert XDO and Liebert XDV). The example below combines one Liebert XDP with 20 Liebert XDV8 cooling modules.

Table 10 Calculating refrigerant charge—example

 

Number of Units

 

 

 

or Piping Length,

Pounds Per

 

Components

feet

Component

Total, lb.

Liebert XDP

1

157

157

 

 

 

 

Liebert XDV8 Cooling Modules

20

2.32

46.4

 

 

 

 

Supply Main, 1-1/8"

100

0.45

45

 

 

 

 

Return Main, 2-1/8"

100

0.28

28

 

 

 

 

Liebert XDV 1/2" supply Liebert XD Flex Pipes

20

0.8

16

 

 

 

 

Liebert XDV 5/8" return Liebert XD Flex Pipes

20

0.03

0.6

 

 

 

 

 

 

Total

293

Table 11 Worksheet to calculate refrigerant charge

Components

Number of Units or Piping Length

Pounds Per Component

Total

Total

19