Specifications
8.0SPECIFICATIONS
Table 17 Liebert XDP160 specifications
Models |
|
| ||||
|
|
|
|
| ||
| 160kW / 46 Tons, 60Hz |
| 140kW / 40 Tons, 50Hz | |||
|
|
| ||||
Cooling Capacity, Nominal | Each capacity is based on 45ºF (7ºC) entering water temperature and | |||||
| 140gpm (530lpm) water flow rate. Capacity is reduced when glycol mixtures | |||||
|
| are used in place of 100% water. | ||||
| The Liebert XDP’s minimum recommended operating load is 20% of system | |||||
Minimum Load | nominal capacity. For example, a Liebert XDP160 60Hz system’s minimum | |||||
load would be 32 kW. Loading below this value can unfavorably affect system | ||||||
| ||||||
| operation. Consult factory for any loading below this recommendation. | |||||
|
|
|
|
|
| |
Electrical Requirements |
|
|
|
|
| |
|
|
|
|
|
| |
Input | 208V/3ph/60Hz |
| 460V/3/ph60Hz |
| 380/415V/3ph/50Hz | |
|
|
|
|
|
| |
Full Load Amps | 4A |
| 2.1A |
| 2.3A | |
|
|
|
|
|
| |
Dimensions, inches (mm) |
|
|
|
|
| |
|
|
|
|
|
| |
Height – Unit only |
| 78 (1981) |
|
| ||
|
|
|
|
| ||
Height – As shipped |
| 83 (2108) |
|
| ||
|
|
|
|
| ||
Width |
| 38 (965) |
|
| ||
|
|
|
|
| ||
Depth |
| 34 (864) |
|
| ||
|
|
|
|
|
| |
Weight, lb (kg) |
|
|
|
|
| |
|
|
|
|
|
| |
Unit only |
| 821 (372) |
|
| ||
|
| |||||
Shipping weight | Domestic: 990 (449); Export: 1067 (484) | |||||
|
|
|
|
|
| |
Installed, with refrigerant and |
| 1038 (471) |
|
| ||
chilled water |
|
|
| |||
|
|
|
|
| ||
Pipe Connections |
|
|
|
|
| |
|
|
|
|
|
| |
Refrigerant supply to Liebert XD |
|
|
| |||
cooling module |
|
|
| |||
|
|
|
|
| ||
Refrigerant return from Liebert XD |
|
|
| |||
cooling module |
|
|
| |||
|
|
|
|
| ||
Chilled water supply and return |
|
|
| |||
|
| |||||
Control Valve | ||||||
| 150 PSIG maximum allowable pressure | |||||
|
| |||||
Pressure Drop – Chilled Water | 20 psig (137kPa, 1.38bar), with 140 gpm (530lpm) water flow rate, | |||||
Side |
|
| control valve fully open |
| ||
Temperature Rise – Chilled |
| 8.0 (4.4) |
| 6.9 (3.8) | ||
Water Side at rated flow, °F (°C) |
|
| ||||
|
|
|
|
| ||
Number of Liebert XD cooling units connected, maximum (minimum) |
| |||||
Liebert XDCF10 |
| 16 (4) |
|
| ||
|
|
|
|
| ||
Liebert XDH20 |
| 8 (2) |
|
| ||
|
|
|
|
| ||
Liebert XDH32 |
| 5 (1) |
|
| ||
|
|
|
|
| ||
Liebert XDV8 |
| 20 (4) |
|
| ||
|
|
|
|
| ||
Liebert XDV10 |
| 16 (4) |
|
| ||
|
|
|
|
| ||
Liebert XDO16 |
| 10 (2) |
|
| ||
|
|
|
|
| ||
Liebert XDO20 |
| 8 (2) |
|
| ||
|
| |||||
Cabinet Exterior Finish | Black, matte finish, | |||||
|
|
|
|
|
| |
Operating Ambient |
| 86 (30) |
|
| ||
Temperature, Maximum, °F (°C) |
|
|
| |||
|
|
|
|
| ||
Agency |
|
|
|
|
| |
Approvals | CSA 60Hz |
| CE 50Hz | |||
|
|
|
|
|
|
33