Piping
2.0PIPING
2.1European Union Fluorinated Greenhouse Gas Requirements
Stationary air conditioning, refrigeration, heat pump equipments and stationary fire protection sys- tems in the European Community market and operating with fluorinated greenhouse gases
The
Refer to the full regulation for additional details.
2.2Connection Sizes
The copper pipe connections on the Liebert XDP are:
Building Chilled Water Supply | |
Building Chilled Water Return | |
Refrigerant Supply | |
Refrigerant Return |
2.2.1Recommended Pipe Size
Connect the main pipes between the Liebert XDP and the Liebert XD cooling modules according to site specific documentation and the configuration guide for the Liebert XD system.
Elbows and restrictions must be minimized to get good fluid flow.
Table 3 Supply, return pipe sizes for refrigerant loop
Pipe Function | Size / Equivalent Pipe Length |
Liebert XDP supply line, from Liebert XDP supply | |
to farthest Liebert XD cooling module | |
Liebert XDP return line, from farthest Liebert XD cooling | |
module to Liebert XDP return | |
From any model Liebert XDO/Liebert XDH supply | 1/2" OD for lengths up to 10 feet |
to supply line of Liebert XDP | 7/8" OD for lengths over 10 but less than 25 feet |
From any model Liebert XDO/Liebert XDH return | 7/8" OD for lengths up to 10 feet |
to return line of Liebert XDP | |
From any model Liebert XDV/Liebert XDCF supply | 1/2" OD for lengths up to 10 feet |
to supply line of Liebert XDP | 5/8" OD for lengths over 10 but less than 35 feet |
From any model Liebert XDV/Liebert XDCF return | 5/8" OD for lengths up to 10 feet |
to return line of Liebert XDP | 7/8" OD for lengths over 10 but less than 35 feet |
11