Miller Electric A.B.B. Robot Interface Gas Control Hub And Spindle Socket Socket Information

Models: A.B.B. Robot Interface Gas Control Hub And Spindle

1 40
Download 40 pages 34.02 Kb
Page 17
Image 17

2-9. 24-Socket Receptacle RC17 Information

D C B A

J H G F E

Q P N M L K

V U T S R

Z Y X W

S-0291

Socket*

Socket Information

 

 

A

Provides connection to 2TA; for customer use.

 

 

B

Current Detect output to robot control unit with respect to Socket D; isolated CR1 contacts rated

1A at 120 VAC.

 

 

 

D

Current Detect output to robot control unit with respect to Socket B; isolated CR1 contacts rated

1A at 120 VAC.

 

 

 

E

Contactor Control; +24 volts dc input from robot control unit with respect to Socket J (Circuit

Common).

 

 

 

F

Jog Forward; +24 volts dc input from robot control unit with respect to Socket J (Circuit

Common).

 

 

 

G

Gas Control; +24 volts dc input from robot control unit with respect to Socket J (Circuit Common).

 

 

H

Wire Stick Check; +24 volts dc input from robot control unit with respect to Socket J (Circuit Com-

mon).

 

 

 

J

Circuit Common for Sockets E, F, G, and H; all circuit voltages referenced to this point.

 

 

K

Jog Forward; momentary contact output to robot control unit with respect to Socket Q (Digital

Common).

 

 

 

L

Set-Up and Weave Set-Up output to robot control unit with respect to Socket Q (Digital Common).

 

 

M

Weave Set-Up output to robot control unit with respect to Socket Q (Digital Common).

 

 

N

Wire Stick Signal output to robot control unit with respect to Socket Q (Digital Common); indicates

wire is stuck to work; isolated CR2 contacts rated 1A at 120 VAC.

 

 

 

P

Weld Standby output to robot control unit with respect to Socket Q (Digital Common); indicates

robot interface is in standby; isolated CR5 contacts rated 3A at 120 VAC.

 

 

 

Q

Digital Common for Sockets K, L, M, N, and P.

 

 

R

+ Peak Amps; 0-10 volts dc input from robot control unit with respect to Socket S (analog

common) equals 0-500 amperes dc output.

 

 

 

S

Peak Amps; analog common for Socket R (+ Peak Amps).

 

 

W

Wire Feed Speed; analog common for Socket X (+ Wire Feed Speed).

 

 

X

+ Wire Feed Speed; 0-10 volts dc input from robot control unit with respect to Socket W (analog

common) equals 0-1000 IPM.

 

 

 

Y

Arc Volts; analog common for Socket Z (+ Arc Volts).

 

 

Z

+ Arc Volts; 0-10 volts dc input from robot control unit with respect to Socket Y (analog common)

equals 0-50 volts dc output.

 

 

 

*The remaining sockets are not used.

OM-884 Page 13

Page 17
Image 17
Miller Electric A.B.B. Robot Interface Gas Control Hub And Spindle manual Socket Receptacle RC17 Information