3-10. Electrical Service Guide

NOTE

All values calculated at 60% duty cycle.

60 Hertz Models

 

Without Power Factor

With Power Factor Correction

 

 

Correction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Voltage

200

 

230

460

575

200

230

460

575

 

 

 

 

 

 

 

 

 

 

Input Amperes At Rated Output

85

 

74

37

30

55

48

24

19

 

 

 

 

 

 

 

 

 

 

Max Recommended Standard Fuse Or Circuit

125

 

110

60

45

80

70

35

30

Breaker Rating In Amperes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min Input Conductor Size In AWG/Kcmil

4

 

6

10

10

8

8

12

14

 

 

 

 

 

 

 

 

 

 

Max Recommended Input Conductor Length

173

 

158

291

455

86

114

186

189

In Feet (Meters)

(53)

 

(48)

(89)

(139)

(26)

(35)

(58)

(48)

 

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil

6

 

6

10

10

8

8

12

14

 

 

 

 

 

 

 

 

 

 

Reference: 1996 National Electrical Code (NEC)

 

 

 

 

 

 

 

 

S-0092-J

 

 

 

 

 

 

 

 

 

 

50 Hertz Models

Without Power Factor Correction

With Power Factor

 

Correction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Voltage

220

260

380

415

520

220

 

380

 

415

 

 

 

 

 

 

 

 

 

 

 

Input Amperes At Rated Output

77

65

45

41

33

64

 

37

 

34

 

 

 

 

 

 

 

 

 

 

 

Max Recommended Standard Fuse Or Circuit

125

100

70

60

50

90

 

60

 

50

Breaker Rating In Amperes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Min Input Conductor Size In AWG/Kcmil

6

6

8

8

10

6

 

10

 

10

 

 

 

 

 

 

 

 

 

 

 

Max Recommended Input Conductor Length

145

202

291

347

372

145

 

291

 

347

In Feet (Meters)

(44)

(62)

(89)

(106)

(113)

(44)

 

(89)

 

(106)

 

 

 

 

 

 

 

 

 

 

 

Min Grounding Conductor Size In AWG/Kcmil

6

8

8

10

10

6

 

8

 

10

 

 

 

 

 

 

 

 

 

 

 

Reference: 1996 National Electrical Code (NEC)

 

 

 

 

 

 

 

 

 

S-0092-J

 

 

 

 

 

 

 

 

 

 

 

Syncrowave 250

TM-353 Page 11

Page 15
Image 15
Miller Electric TM-353E manual Electrical Service Guide, All values calculated at 60% duty cycle