56
••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••
•“Main-Alarm appears when Alarm Recording Area
(System Menu Memory Data Management Setting
for Main Memory Change Partition Setting) is set to
other than 0 %.
•“Main-LPA appears when Long Pre-Alarm Area
(System Menu Memory Data Management Setting
for Main Memory Change Partition Setting) is set to
other than 0 %.
step3. Set the desired capacity.
Set the remaining capacity of each device to
output signal.

Call Out Settings

This item is used to output warning signals from the CALL
OUT terminal to the device connected when the capacity
becomes full or reaches to the specified value.
Call Out Settings
2
Setup Menu
System
Rear Terminal Setting
4
3
step1. Set the desired capacity for each area.
Off: Does not output a signal.
•“Alarm Recording Area appears when Alarm
Recording Area (System Menu Memory Data
Management Setting for Main Memory Change
Partition Setting) is set to other than 0 %.
•“LPA Recording Area appears when Long Pre-Alarm
Area (System Menu Memory Data Management
Setting for Main Memory Change Partition Setting)
is set to other than 0 %.
Call out settings use the photo-coupler output to
decrease the malfunctions due to wiring. See CALL
OUT signal output ( see page 17) for the correct
connection.
For the relationship between the warning display and
CALL OUT signal output, see pages 106 and 107.
The warning display of the item written Fixed in the
CALL OUT output column displays unconditionally.
For the item written Selectable in the CALL OUT
output column, you can set the condition that CALL
OUT signal is output. For example, the buzzer can
be set to sound when reaching the value set in
Normal Recording Area, Alarm Recording Area,
LPA Recording Area, or Copy B (Setup
Menu System Rear Terminal Setting Call Out
Settings) when Buzzer (Setup Menu System Rear
Terminal Setting) is set to Warning.
Rear Terminal Setting

Mode Out Settings

This item is used to output the status of this unit from the
MODE OUT terminals on the rear panel. There are 4 MODE
OUT terminals. Set output signal for each terminal indi-
vidually.
Mode Out Settings
1
Setup Menu
System
Rear Terminal Setting
4
3
(Mode Out 1 to 4)
step1. Set the desired mode out settings for Mode out 1 to
4.
Recording: Outputs signal during recording.
Playing: Outputs signal during playback.
Low Memory: Outputs signal when the remaining
HDD capacity reaches the value specified in Low
Memory Alarm Setting.
Power: Outputs signal when the power of the unit
turns on.
Alarm: Outputs signals during alarm recording.
LAN: Controls the output of the signal via the PC
connected.
Off: Does not output signal.
By using Polarity, the output condition of MODE
OUT can be changed.
Open: Opens output when the mode out is active.
Close: Closes output when the mode out is active.
MODE OUT is the ground terminal using relay. Use
the terminal under the required conditions (less than
DC24V and 500 mA).
Low memory warning from MODE OUT terminal is
output only during recording.
(Low Memory Alarm Setting)
This item is used to output a warning when the remaining
capacity becomes low during recording. Set the desired
device and remaining capacity for this warning.
A warning is output using the following methods when
the remaining capacity becomes low during recording.
The recorded capacity of HDD flashes when the
operation mode display is set to be displayed.
A buzzer sounds when Buzzer is set to Remain.
step2. Set the desired device.
Main-Normal: Displays a warning of low normal
area capacity.
Main-Alarm: Displays a warning of low alarm area
capacity.
Main-LPA: Displays a warning of low LPA area
capacity.
Copy B: Displays a warning of low copy B device
capacity.
Off: Does not display a warning of low HDD
capacity.
System (continued) Setup Menu