Mitsubishi Electronics MSZ-FA35VA, MSZ-FA25VA Check of installation of the horizontal vane

Models: MSZ-FA25VA MSZ-FA35VA

1 40
Download 40 pages 15.69 Kb
Page 25
Image 25

When All lamps flash ON and OFF every 0.5-second. Indoor unit and outdoor unit do not operate.

E Check of installation of the horizontal vane

Start

 

Turn OFF the

 

power supply.

 

Is the stopper of the horizontal vane

No

 

locked to the indoor unit correctly?

 

Yes

 

To check the continuity of the interlock switch (Fan), measure the resistance of connector 1 - 2 connected to CN1R1 on the indoor

electronic control P.C. board.

Relock the stopper of the horizontal vane to the indoor unit. Refer to 9-1.5.

Turn ON the power supply.

No

Are all lamp flashing?

OK

Yes

Turn OFF the power supply.

No()

Is there resistance 0 "?

Yes

Replace the indoor electronic control P.C. board.

Replace the interlock switch(Fan).

25

Page 25
Image 25
Mitsubishi Electronics MSZ-FA35VA, MSZ-FA25VA service manual Check of installation of the horizontal vane