Mitsubishi Electronics MSZ-FA25VA, MSZ-FA35VA service manual Troubleshooting check table

Models: MSZ-FA25VA MSZ-FA35VA

1 40
Download 40 pages 15.69 Kb
Page 18
Image 18

9-4. Troubleshooting check table

Lighted

· Flashing of POWER lamp indicates abnormalities.

Blinking

Not lighted

NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting. Self check table

No.

Abnormal

Operation indicator lamp

Symptom

Detection method

Check point

 

point

 

 

 

 

 

 

POWER lamp flashes.

 

 

 

 

Mis-Wiring

0.5-second ON

Outdoor unit

When the serial signal form the outdoor unit is

• Refer to 9-6.D"How to check

1

or serial

 

does not

mis-wiring and serial signal

 

not received for a maximum of 6 minutes.

 

signal

 

operate.

error".

 

 

0.5-second OFF

 

 

 

 

Outdoor

 

 

When it cannot properly read data in the

• Check the blinking pattern of

 

 

Outdoor unit

the LED on the inverter P.C.

2

control

POWER lamp lights up

nonvolatile memory of the inverter P.C. board

board or the outdoor lectronic

does not

or the outdoor electronic control P.C. board.

 

system

 

control P.C. board.

 

 

operate.

 

 

 

 

 

 

 

Indoor coil

POWER lamp flashes.

 

 

 

 

thermistor

 

 

 

 

2-time flash

Indoor unit

When the indoor coil or the room temperature

• Refer to 9-7.the

 

 

3

 

 

and outdoor

thermistor is short or open circuit.

characteristics of indoor coil

Room

 

unit do not

 

thermistor, and the room

 

tempera-

2.5-second OFF

operate.

 

temperature thermistor.

 

ture

 

 

 

 

 

 

 

 

 

thermistor

 

 

 

 

 

 

POWER lamp flashes.

Indoor unit

 

 

 

 

3-time flash

When the rotational frequency feedback

• Refer to 9-7.A"Check of

 

Indoor fan

 

and outdoor

4

 

signal is not emit during the indoor fan

motor

 

unit do not

indoor fan motor".

 

 

operation.

 

 

 

operate.

 

 

 

 

 

 

 

 

2.5-second OFF

 

 

 

 

 

POWER lamp flashes.

Indoor unit

When it consecutively occurs 3 times that the

• Refer to "Check of inverter/

 

Outdoor

5-time flash

 

compressor".

5

power

 

and outdoor

compressor stops for overcurrent protection or

Refer to service manual

 

unit do not

start-up failure protection witth in 1 minute

 

system

 

OB372 or OB377.

 

 

operate.

after start-up.

 

 

2.5-second OFF

Check the stop valve.

 

 

 

 

 

 

 

 

 

 

 

POWER lamp flashes.

 

 

 

 

 

6-time flash

Indoor unit

When the outdoor thermistors short or open

• Refer to "Check of outdoor

 

Outdoor

 

and outdoor

thermistor".

6

 

unit do not

circuit during the compressor operation.

Refer to service manual

thermistors

 

 

 

operate.

 

OB372 or OB377.

 

 

2.5-second OFF

 

 

 

 

 

 

 

 

POWER lamp flashes.

Indoor unit

 

• Replace the inverter P.C.

 

Outdoor

7-time flash

When it cannot properly read data in the

board or the outdoor

 

and outdoor

7

control

 

nonvolatile memory of the inverter P.C. board

electronic control P.C. board.

 

unit do not

 

system

 

or the outdoor electronic control P.C. board.

Refer to service manual

 

 

operate.

 

 

2.5-second OFF

 

OB372 or OB377.

 

 

 

 

 

 

POWER lamp flashes.

Indoor unit

 

 

 

Other

14-time flash

An abnormality other than above mentioned is

• Confirm the abnormarity in

8

 

and outdoor

detail using the failure mode

abnonmality

 

unit do not

deteced.

 

 

 

operate.

 

recall function.

 

 

2.5-second OFF

 

 

 

 

 

 

 

NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.

18

Page 18
Image 18
Mitsubishi Electronics MSZ-FA25VA Troubleshooting check table, · Flashing of Power lamp indicates abnormalities