The unit does not operate with the remote controller.
Also, POWER lamp does not light up by pressing EMERGENCY OPERATION switch.
C Check of indoor P.C. board and indoor fan motor
Turn OFF the power supply.
Remove indoor fan motor connector CN211, vane motor connector CN151 and the
Does the unit operate with the remote controller? | Yes |
Does POWER lamp light up by pressing EMERGENCY |
|
OPERATION switch? |
|
No |
|
Measure the resistance of the
Refer to
Measure the resistance between CN211 3 and 4 of the indoor fan motor connector.
Measure the resistance of the horizontal vane motor coil and the vertical vane motor coil. Refer to
Replace the varistor(NR11) and fuse(F11).
Yes
Short/open circuit:
Replace the
and the indoor electronic control P.C. board.
Short/open circuit:
Replace the indoor fan motor.
Short/open circuit:
Replace the horizontal vane motor, the vertical vane motor and the indoor electronic control P.C. board.
Turn OFF the power supply.
Check both “parts side” and “pattern side” of the indoor electronic control P.C. board visually.
|
| Are the varistor(NR11) burnt No |
|
|
|
|
|
| |||
|
| and the fuse(F11) blown? |
|
|
|
|
|
|
| ||
|
| Be sure to check both the fuse |
|
|
|
|
|
| |||
|
| and the varistor in any case. |
|
|
|
|
|
| |||
|
| Is the fuse(F11) blown only? | No |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| ||
|
|
| Yes |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
| ||
|
| Measure the resistance between |
|
|
|
| w1. The fan motor connector's1 lead wire is red, whereas 3 is black. | ||||
|
| 1(+) and |
|
|
|
| |||||
|
|
|
|
|
|
|
| ||||
|
| motor connector. |
|
|
|
| w2. Connect "+" of the tester to fan motor connector's1 lead | ||||
|
| w1,w2 |
|
|
|
| |||||
|
|
|
|
|
| wire, and | |||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| measured properly. | |
|
|
|
|
|
| No | |||||
|
|
|
|
|
|
|
| ||||
|
| Is the resistance 1 M" |
|
|
| ||||||
|
| Replace the fuse (F11) and the indoor fan motor. | |||||||||
|
|
|
|
|
|
| |||||
|
| or more? |
|
|
|
|
| ||||
|
|
|
|
|
|
|
| ||||
|
|
| Yes |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
Replace the fuse (F11).
Measure the resistance of cement resistor(R111) on the indoor electronic control P.C. board.
Is the resistance approx. 4 "?
Yes
No
Replace the indoor electronic control P.C. board and the indoor fan motor.
Replace the indoor electronic control P.C. board.
30