9-1. COOL ( ) OPERATION

(1)Press OPERATE/STOP(ON/OFF) button.

POWER lamp of the indoor unit turns on with a beep tone.

(2)Select COOL mode with OPERATION SELECT button.

(3)Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature. The setting range is 16 ~ 31 °C.

1. Coil frost prevention

The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the coil from frosting.

When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.

The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of indoor heat exchanger rises.

2.Low outside temperature operation

When the outside temperature is lower, low outside temperature operation starts, and the outdoor fan slows or stops.

9-2. DRY ( ) OPERATION

(1)Press OPERATE/STOP(ON/OFF) button.

POWER lamp of the indoor unit turns on with a beep tone.

(2)Select DRY mode with OPERATION SELECT button.

(3)The set temperature is determined from the initial room temperature.

1.Coil frost prevention

Coil frost prevention is as same as COOL mode. (9-1.1.)

2.Low outside temperature operation

Low outside temperature operation is as same as COOL mode. (9-1.2.)

9-3. HEAT ( ) OPERATION

(1)Press OPERATE/STOP(ON/OFF) button.

POWER lamp of the indoor unit turns on with a beep tone.

(2)Select HEAT mode with OPERATION SELECT button.

(3)Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature. The setting range is 16 ~ 31 °C.

1.Cold air prevention control

When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room tem- perature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.

2.High pressure protection

The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the con- densing pressure from increasing excessively.

When the temperature of indoor heat exchanger becomes too high, the high pressure protection works.

The indoor fan operates following the cold air prevention control. This mode continues until the temperature of indoor heat exchanger falls.

3.Defrosting

Defrosting starts when the temperature of outdoor heat exchanger becomes too low.

The compressor stops once, the indoor/outdoor fans stop, the 4-way valve reverses, and the compressor re-starts. This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.

9-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION

Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation.

Mode selection

(1)Initial mode

When unit starts the operation with AUTO operation from off;

If the room temperature is higher than the set temperature, operation starts in COOL mode.

If the room temperature is equal to or lower than the set temperature, operation starts in HEAT mode.

(2)Mode change

COOL mode changes to HEAT mode when about 15 minutes have passed with the room temperature 2 °C below the set temperature.

HEAT mode changes to COOL mode when about 15 minutes have passed with the room temperature 2 °C above the set temperature.

NOTE 1

If two or more indoor units are operating in multi system, there might be a case that the indoor unit, which is operating

in

(AUTO), cannot change over to the other operating mode (COOL HEAT) and becomes a state of standby.

Refer to NOTE 2 “FOR MULTI SYSTEM AIR CONDITIONER”.

12

Page 12
Image 12
Mitsubishi Electronics MSZ-FD25VA Cool Operation, DRY Operation, Heat Operation, Auto Change Over ··· Auto Mode Operation