12
1. Coil frost prevention
Coil frost prevention is as same as COOLmode. (9-1.1.)
2. Low outside temperature operation
Low outside temperature operation is as same as COOLmode. (9-1.2.)
1. Cold air prevention control
When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room tem-
perature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed.
9-2. DRY ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
POWER lamp of the indoor unit turns on with a beep tone.
(2) Select DRYmode with OPERATION SELECT button.
(3) The set temperature is determined from the initial room temperature.
9-3. HEAT ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
POWER lamp of the indoor unit turns on with a beep tone.
(2) Select HEATmode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOLbutton) to select the desired temperature.
The setting range is 16 ~ 31 °C.
1. Coil frost prevention
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the coil
from frosting.
When the temperature of indoor heat exchanger becomes too low, the coil frost prevention mode works.
The indoor fan operates at the set speed and the compressor stops. This mode continues until the temperature of indoor
heat exchanger rises.
2. Low outside temperature operation
When the outside temperature is lower, low outside temperature operation starts, and the outdoor fan slows or stops.
9-1. COOL ( ) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
POWER lamp of the indoor unit turns on with a beep tone.
(2) Select COOLmode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOLbutton) to select the desired temperature.
The setting range is 16 ~ 31 °C.
2. High pressure protection
The compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the con-
densing pressure from increasing excessively.
When the temperature of indoor heat exchanger becomes too high, the high pressure protection works.
The indoor fan operates following the cold air prevention control. This mode continues until the temperature of indoor
heat exchanger falls.
3. Defrosting
Defrosting starts when the temperature of outdoor heat exchanger becomes too low.
The compressor stops once, the indoor/outdoor fans stop, the 4-way valve reverses, and the compressor re-starts.
This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.
9-4. AUTO CHANGE OVER ··· AUTO MODE OPERATION
Once desired temperature is set, unit operation is switched automatically between COOLand HEAT operation.
Mode selection
(1) Initial mode
When unit starts the operation with AUTO operation from off;
If the room temperature is higher than the set temperature, operation starts in COOLmode.
If the room temperature is equal to or lower than the set temperature, operation starts in HEATmode.
(2) Mode change
COOLmode changes to HEAT mode when about 15 minutes have passed with the room temperature 2 °C below the
set temperature.
HEATmode changes to COOL mode when about 15 minutes have passed with the room temperature 2 °C above the
set temperature.
NOTE 1
If two or more indoor units are operating in multi system, there might be a case that the indoor unit, which is operating
in (AUTO), cannot change over to the other operating mode (COOL HEAT) and becomes a state of standby.
Refer to NOTE 2 FOR MULTI SYSTEM AIR CONDITIONER.
OBH488-1.qxp 07.8.9 4:06 PM Page 12