10-4. TROUBLESHOOTING CHECK TABLE
Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
When the indoor unit has started operation and the following detection method has detected an abnormality (the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.
L AREA R | POWER CLEAN PLASMA | Lighted |
|
| Blinking |
|
| Not lighted |
No. | Abnormal | Operation indicator lamp |
| point |
|
|
| POWER lamp flashes. |
Symptom | Condition | Correspondence |
| Miswiring | |
|
| |
1 | or serial |
|
| signal |
|
|
| |
| Indoor coil | POWER lamp flashes. |
2 | thermistor | |
Room |
| |
|
| |
| temperature |
|
| thermistor | |
|
| POWER lamp flashes. |
|
| |
3 | Indoor fan |
|
motor |
| |
|
| |
|
| |
| Indoor | POWER lamp flashes. |
| ||
4 | control |
|
| system |
|
|
| |
|
| POWER lamp flashes. |
5 | Outdoor | |
power |
|
system
POWER lamp flashes.
Outdoor
6 thermistors
| Outdoor | POWER lamp flashes. |
| ||
| control | |
7 |
| |
system |
| |
|
|
POWER lamp flashes.
Other
8 abnormality
Outdoor
9 control POWER lamp lights up. system
Indoor unit and outdoor unit do not operate.
Outdoor unit does not operate.
The serial signal from the outdoor unit is not received for 6 minutes.
The indoor coil or the room temperature thermistor is short or open circuit.
The rotational frequency feedback signal is not emitted during the indoor fan operation.
It cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
It consecutively occurs 3 times that the compressor stops for overcurrent protection or
The outdoor thermistors short or open circuit during the compressor operation.
It cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.
An abnormality other than above mentioned is detected.
It cannot properly read data in the nonvolatile memory of the inverter P.C. board or the outdoor electronic control P.C. board.
•Refer to
•Refer to
•Refer to
•Replace the indoor electronic control P.C. board.
•Refer to "How to check of inverter/compressor".
Refer to outdoor unit service manual.
•Check the stop valve.
•Refer to "Check of outdoor thermistor".
Refer to outdoor unit service manual.
•Replace the inverter P.C. board or the outdoor electronic control P.C. board. Refer to outdoor unit service manual.
•Check the stop valve.
•Confirm the abnormality in detail using the failure mode recall function for outdoor unit.
•Check the blinking pattern of the LED on the inverter P.C. board or the outdoor electronic
control P.C. board.
25