10-2. FAILURE MODE RECALL FUNCTION
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table
This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Operational procedure
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Turn ON the power supply.
<Preparation of the remote controller>
1 While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button.
2First, release RESET button.
And release the other two buttons after all LCD in operation display section of the remote controller is displayed after 3 seconds.
Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. W1
W1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal. Beep is emitted at the same timing
as the blinking of POWER lamp. W2
Judgment of indoor/outdoor abnormality | Yes |
(Blinks) |
No
(OFF)
Indoor unit is normal.
But the outdoor unit might be abnormal because there are some abnormalities that can't be recalled with this way.
Confirm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function.
| Before blinking, does POWER lamp stay | Yes |
|
|
|
| |||
| ON for 3 seconds? |
|
|
|
| ||||
|
|
|
|
|
| ||||
| Stays ON for 3 seconds (without beep): |
|
|
|
|
| |||
| The outdoor unit is abnormal. |
|
|
|
|
| |||
|
|
|
| No |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| The indoor unit is abnormal. |
|
| The outdoor unit is abnormal. | |||||
| Check the blinking pattern, and confirm the abnormal point with the indoor unit |
| Check the blinking pattern, and confirm the abnormal point with the | ||||||
| failure mode |
|
| outdoor unit failure mode table (Refer to outdoor unit service manual.) | |||||
| Make sure to check at least two consecutive blinking cycles. W2 |
|
| Make sure to check at least two consecutive blinking cycles. W3 | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Releasing the failure mode recall function |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| Release the failure mode recall function by the following procedures. |
|
|
|
|
| |||
| Turn OFF the power supply and turn it ON again. |
|
|
|
|
| |||
| Press RESET button of the remote controller. |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Repair the defective parts. |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Deleting the memorized abnormal condition |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above.
2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
4Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.
NOTE: 1.Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly. 2.If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2. Blinking pattern when the indoor unit is abnormal:
|
|
|
| Blinking at 0.5- |
|
|
|
|
|
|
|
|
|
|
| Blinking at 0.5- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||||||||||
|
|
| second interval |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||||||||||||||||||||
ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
OFF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
| Beeps |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Beeps |
|
|
| Beeps |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||||
|
|
| Repeated cycle |
|
|
|
|
|
| Repeated cycle | Repeated cycle |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||||||||||||||||||
W3.Blinking pattern when the outdoor unit is abnormal: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Blinking at 0.5- | |||||||||||||||||||||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Blinking at 0.5- |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||||||||||||||||||||
|
|
|
|
|
|
|
| second interval |
|
|
|
|
| second interval | |||||||||||||||||||||||||||||||||||||||||||||||||
ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OFF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| No beep |
|
|
|
|
|
| Beeps |
|
|
|
|
|
|
|
|
|
| No beep |
|
|
|
|
| Beeps | ||||||||||||||||||||||||||||||||
|
|
|
|
|
|
| Repeated cycle |
|
|
|
|
|
|
|
|
|
| Repeated cycle |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Repeated cycle |
21