2. Flow chart of PLASMA operation failure mode recall function
Operational procedure
The plasma electrode unit might be abnormal. Confirm if plasma electrode unit is abnormal according to the following procedures.
Confirm that the remote controller is in the failure mode recall function.
With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 23 :. W1
W1. Regardless of normal or abnormal condition, a short beep is emitted as the signal is received.
| Does POWER lamp on the indoor unit blink at the | No | ||||||
| interval of 0.5 seconds? |
| (OFF) | |||||
| Blinks: The plasma electrode unit is abnormal. |
|
|
|
| |||
| Beep is emitted at the same timing as the |
|
|
|
| |||
| blinking of POWER lamp. | W2 |
|
|
|
| ||
|
|
| Yes |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| (Blinks) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| The plasma electrode unit is abnormal. |
|
|
|
|
| ||
| Check the blinking pattern, and refer to confirm the abnormal point |
|
| The plasma electrode unit is normal. | ||||
| with the PLASMA operation failure mode table |
|
| |||||
|
|
|
|
| ||||
| Make sure to check at least two consecutive blinking cycles. W2 |
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Releasing the failure mode recall function |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
Release the failure mode recall function according to the left mentioned procedure.
Repair the defective parts.
Deleting the memorized abnormal condition
1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above.
2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
4Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.
NOTE1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
W2.Blinking pattern when plasma unit is abnormal:
Blinking at 0.5- | Blinking at 0.5- |
|
| ||
ON |
|
|
OFF |
|
|
Beeps | Beeps | Beeps |
Repeated cycle | Repeated cycle | Repeated cycle |
3. PLASMA operation check
PLASMA operation goes ON when PLASMA button on the remote controller is pressed with any set temperature displayed during failure mode recall function.
PLASMA lamp | Correspondence | |
Continuously blinking | Follow "Check of PLASMA operation" to identify the error.(Refer to | |
|
| |
There is failure in PLASMA operation control circuit on the indoor electronic control | ||
P.C. board.(Refer to | ||
| ||
Not lighted | Normal | |
|
|