Mitsubishi Electronics MSZ-FD35VAS Flow chart of Plasma operation failure mode recall function

Models: MSZ-FD25VA MSZ-FD35VA MSZ-FD35VAS MSZ-FD25VAS

1 40
Download 40 pages 13.16 Kb
Page 22
Image 22

2. Flow chart of PLASMA operation failure mode recall function

Operational procedure

The plasma electrode unit might be abnormal. Confirm if plasma electrode unit is abnormal according to the following procedures.

Confirm that the remote controller is in the failure mode recall function.

With the remote controller headed towards the indoor unit, press TOO COOL or TOO WARM button to adjust the set temperature to 23 :. W1

W1. Regardless of normal or abnormal condition, a short beep is emitted as the signal is received.

 

Does POWER lamp on the indoor unit blink at the

No

 

interval of 0.5 seconds?

 

(OFF)

 

Blinks: The plasma electrode unit is abnormal.

 

 

 

 

 

Beep is emitted at the same timing as the

 

 

 

 

 

blinking of POWER lamp.

W2

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Blinks)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The plasma electrode unit is abnormal.

 

 

 

 

 

 

Check the blinking pattern, and refer to confirm the abnormal point

 

 

The plasma electrode unit is normal.

 

with the PLASMA operation failure mode table (10-2.5.).

 

 

 

 

 

 

 

 

Make sure to check at least two consecutive blinking cycles. W2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Releasing the failure mode recall function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again.

Press RESET button of the remote controller.

Release the failure mode recall function according to the left mentioned procedure.

Repair the defective parts.

Deleting the memorized abnormal condition

1After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall function" mentioned above.

2Press OPERATE/STOP(ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.

3Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.

4Release the failure mode recall function according to "Releasing the failure mode recall function" mentioned above.

NOTE1. Make sure to release the failure mode recall function once it's set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

W2.Blinking pattern when plasma unit is abnormal:

Blinking at 0.5-

Blinking at 0.5-

 

2.5-second OFF second interval

2.5-second OFF second interval

 

ON

 

 

OFF

 

 

Beeps

Beeps

Beeps

Repeated cycle

Repeated cycle

Repeated cycle

3. PLASMA operation check

PLASMA operation goes ON when PLASMA button on the remote controller is pressed with any set temperature displayed during failure mode recall function.

PLASMA lamp

Correspondence

Continuously blinking

Follow "Check of PLASMA operation" to identify the error.(Refer to 10-6.F)

 

 

2-time flash

There is failure in PLASMA operation control circuit on the indoor electronic control

P.C. board.(Refer to 10-6.F)

 

Not lighted

Normal

 

 