PEH-10,15,20MYA-EU

[PRODUCT]

 

 

 

 

PACKAGE AIR COOLED HEATPUMP UNITS

Product type

 

 

 

 

 

 

PEH SERIES

 

 

Product number :

Indoor unit

 

 

 

PEH-10MYA-EU

 

 

PEH-15MYA-EU

 

PEH-20MYA-EU

 

Outdoor unit

 

PUH-10MYC1-EU

 

PUH-10MYE-EU

 

PUH-15MYC1-EU

 

PUH-20MYC1-EU

Cooling capacity (AS1861)

 

 

 

kW

28.8

 

 

 

 

44.0

 

57.6

Sensible Cooling capacity (AS1861)

 

 

kW

23.0

 

 

 

 

35.2

 

46.0

Cooling power consumption (Input)

 

 

kW

10.1

 

 

 

 

16.8

 

22.7

Heating capacity (AS1861)

 

 

kW

28.8

 

 

 

 

44.0

 

57.6

Heating power consumption

 

 

kW

8.3

 

 

 

 

14.1

 

19.3

Basic temperature condition cooling

Indoor

 

 

 

27

DB/19

WB

 

 

Basic temperature condition cooling

Outdoor

 

 

 

 

35

 

DB

 

 

 

Basic temperature condition heating

Indoor

 

 

 

 

21

 

DB

 

 

 

Basic temperature condition heating

Outdoor

 

 

 

7

DB/6

WB

 

 

[ELECTRICAL ]

 

 

 

 

 

 

 

 

 

 

 

 

 

<Indoor unit>

 

 

 

 

 

 

 

 

 

 

 

 

 

Design voltage

 

 

 

Volts

 

 

 

415

 

 

 

Cycles

 

 

 

Hz

 

 

 

 

50

 

 

 

Power supply

 

 

 

Volts

 

 

 

3PH-415V

 

 

Control voltage

 

 

 

 

 

 

 

240/24

 

 

 

Voltage change

Max.

Volts

 

 

 

415

 

 

 

Voltage change

Min.

Volts

 

 

 

380

 

 

 

Fan motor output

 

 

 

HP(kW)

1.34(1.0)

 

1.34(1.0)

 

2.95(2.20)

 

4.96(3.70)

Fan motor current

 

 

 

Amps

2.0

 

2.0

 

 

 

4.1

 

4.7

<Outdoor unit>

 

 

 

 

 

 

 

 

 

 

 

 

 

Design voltage

 

 

 

Volts

 

 

 

 

415

 

 

 

Cycles

 

 

 

Hz

 

 

 

 

50

 

 

 

Power supply

 

 

 

Volts

 

 

 

3PH-415V

 

 

Voltage change

Max.

Volts

 

 

 

 

415

 

 

 

Voltage change

Min.

Volts

 

 

 

 

380

 

 

 

Fan motor output

 

 

 

HP(kW)

2X0.2(2X0.15)

 

0.47(0.35)

 

 

2X0.47(2X0.35)

Fan motor current

 

 

 

Amps

1.0

 

1.2

 

 

 

2X1.2

[COMPRESSOR]

 

 

 

 

 

 

 

 

 

 

 

 

 

Make

 

 

 

 

 

 

MITSUBISHI

 

 

Model

 

 

 

 

JH527YE

 

 

JH521YE

 

JH527YE

Type

 

 

 

 

HERMETIC LINE START (RECIPROCATING)

Number of compressor

 

 

 

 

1

 

 

 

 

 

2

Nominal motor

 

 

 

HP(kW)

10.1(7.5)

 

 

 

7.4(5.5)

 

10.1(7.5)

Locked rotor current

 

 

 

Amps

85

 

 

 

 

83

 

85

Normal run current (AS1861)

 

 

Amps

19.2

 

 

 

 

15.5

 

19.2

Swept volume

 

 

 

cc/rev

201

 

 

 

 

160.8

 

201

Bore

 

 

 

mm

 

 

 

ø44.45

 

 

 

Stroke

 

 

 

mm

 

 

 

25.9

 

 

 

Speed

 

 

 

rpm

 

 

 

2900

 

 

 

Number of cylinders

 

 

 

 

5

 

 

 

 

4

 

5

Oil charge

 

 

 

ml

4500

 

 

 

 

3000

 

4500

Type of oil

 

 

 

 

DIAMOND MS32(N-1) OR SUNISO 3GS(D)

Crankcase heater

 

 

 

watts

72

 

 

 

 

62

 

72

[REFRIGERATION SYSTEM]

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant

 

 

 

 

 

 

 

R22

 

 

 

Refrigerant charge per circuit

 

 

kg

9.9

 

 

 

 

6.6

 

9.7

Number of refrigerant controls

 

 

 

1

 

 

 

 

 

2

Refrigerant control

 

 

 

 

 

 

Capillary tube

 

 

Reverse cycle valve

 

 

 

 

 

 

4-way valve

 

 

Defrost system

 

 

 

 

 

 

Reverse cycle defrost

 

 

Limit of pipe's length

 

 

 

m

 

 

 

 

50

 

 

 

Limit of pipe's height difference

 

 

mtrs

20 (In case of indoor unit above outdoor unit)

 

 

mtrs

30 (In case of outdoor unit above indoor unit)

 

 

 

 

- 84 -