1-6.Trouble shooting

Before you ask for repair service, check the following points:

State of Machine

Remote Controller

Cause

Troubleshooting

 

 

 

 

 

 

"ON-OFF "display is

Power failure

Press the [ON/OFF] button after power restoration.

 

not lit up

 

 

 

 

 

The power supply is turned OFF.

Turn the power supply ON.

It does not run

No display appears

even when the [ON/

The fuse in the power supply is gone.

Replace fuse.

 

 

OFF] button is

 

 

 

 

pressed.

The earth leakage breaker is gone.

Put in the earth leakage breaker.

 

 

 

 

 

Air flows out but it

The liquid crystal

Improper temperature adjustment.

After checking the set temperature and inlet

temperature on the liquid crystal display, refer to

does not cool

display shows that

 

[To change room temperature] on page 107, and

enough or heat

it is in the state of

 

 

operate the adjustment button.

enough.

operation.

 

 

 

The filter is filled with dust and dirt.

Clean up the filter.

 

 

 

 

 

 

 

 

 

 

 

There are some obstacles at the air inlet and

Remove.

 

 

 

outlet of the indoor and outdoor units.

 

 

 

 

 

 

 

 

 

 

 

 

Windows and doors are open.

Close.

 

 

 

 

 

 

 

 

 

Wait for a while.

Cool air or warm air

The liquid crystal

The restart-preventing circuit is in operation for

(To protect the compressor, a 3-minute restart-

preventing circuit is built into the indoor unit.

does not come out.

display shows that

3 minutes.

Therefore, there are occasions sometimes when

 

it is in operation.

 

 

 

the compressor does not start running immedi-

 

 

 

 

 

 

 

 

ately. There are cases when it does not run for as

 

 

 

 

long as 3 minutes.)

 

 

 

 

 

 

 

 

Indoor unit operation was started anew during

Wait for a while.

 

 

 

the heating and defrosting operation.

(Heating operation starts after ending defrosting

 

 

 

(5 10 HP only)

operation.)

 

 

 

 

Can not change

Can not change to

DIP switch1 is not correct

Change the DIP switch off to on.

to Heat mode

Heat mode when

 

(Refer to Instruction manual for Installation.)

 

press the "MODE" key.

 

 

 

 

 

 

 

Error Display

Indicate

Cause

Troubleshooting

E01

Room temperature sensor open.

Automatically

reset to restoration error.

E02

Room temperature sensor short.

Automatically

reset to restoration error.

E03

Error input from Indoor unit or

Push the On-Off switch.(OFF to ON)

 

Outdoor unit.

 

 

- 111 -