PUH-15, 20

(1) At a single installation

The obstacle is on the outlet side. (Fig 1) The obstacle is in four directions. (Fig 2) The obstacle is in three directions. (Fig 3,4)

ceiling

1500 over

The right and left side

and the back and forth 300 over side must be opened.

Fig 1

However, the outlet side must be opened.

300 over

300 over

Service-panel

 

 

 

However, outlet side

 

 

500 over must be opened.

 

 

300 over

And the obstacle in

 

 

two directions must be

 

 

 

Service Panel

 

lower than the unit.

Fig 2

300over

Service-panel

500 over

Fig 3

Fig 4

(2) Relation of unit when many set up unit. (Fig 5,6,7)

300 over

 

Service-panel

500 over

 

 

300 over

500

300 over

over

Service-panel

Fig 5

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

A A A A

Fig 6 All "A" is 500 over.

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

300 over

A

A

A

300 over

Fig 7 All "A" is 500 over in any case.

2. Preparation before installing

Indoor unit

Please use the specified hanging bolt in any case.

Hanging bolt is local supply.

 

Please use the method below or use the angle and the

 

rectangular lumber, etc. and install the hanging bolt.

Insert etc

 

100-150kg

Reinforcement

Hanging bolt

M10 (PEH-5,PE(H)-7,8,10)

M12 (PE(H)-15,20)

- 90 -

Page 91
Image 91
Mitsubishi Electronics PE-10MYC, PE-8MYC, PE-15MYC Preparation before installing Indoor unit, Over Service-panel 500