SELECTION PROCEDURE

1. Model Selection (With actual examples)

First step, to select the approximate model:

Based on the cooling load and the cooling capacity listed in the capacity table, select the applicable model.

Second step, to select the model:

To select the model, the following conditions must be known:

(1)Total cooling load or sensible cooling load

(2)Indoor conditioned temperature (WB*1, DB)

(3)Designed outdoor temperature (DB)*2

(4)Designed air flow

(5)Designed external static pressure (= Wind pressure loss of air duct)*3

Notes:

*1. The correct WB is required since it has a serious effect on the capacity.

*2. The cooling capacity decreases as the outdoor temperature increases. Therefore, the estimated highest temperature during an air conditioning time frame is the "designed outdoor temperature". However, it is recommended that the abnormal outdoor temperature which may occur once or twice a year be excluded from the calculation to avoid selection of an excessively large capacity model.

*3. The wind pressure loss of an air duct should be calculated correctly. If a value having an excessive allowance is used, an excessively large model will be selected. Moreover, an excessively high air flow will be induced during actual operation causing the generation of high operating sounds and carry-over of condensed water.

(Step-1) Confirmation of operation range

Confirm that the conditions given above for the model to be selected are within the

operation range listed on Page 36.

(Step-2) Calculation of actual air flow, external static pressure, and fan motor input

Based on the designed air flow and external static pressure, obtain the actual air flow, actual external static pressure, and fan motor power input from the fan performance table for the model selected. For an explanation of how to use the fan performance table, see the following examples.

Example: PE-8MYC, 50Hz

Example 1. (To operate with values near to the designed air flow and external static pressure.)

Condition : Designed air flow 70CMM

Designed external static pressure 60Pa

Calculation : The designed point is A. Therefore, duct resistance line passing A is

dotted line.

 

(Pa)

 

 

Fan Performance Curve 50Hz

 

450

 

 

 

 

 

 

 

 

 

 

 

 

 

Therefore, actual point is B for Δconnection

 

 

 

 

 

Recommended

Range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Actual air flow = 77CMM

 

400

 

 

 

 

 

For

connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation

 

line

 

Actual external static pressure = 70Pa

 

350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes: Duct resustance line is secondary curve.

 

300

 

 

 

 

 

 

 

 

 

 

B

 

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

static

 

 

 

 

 

 

 

 

60Pa

 

 

 

 

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

 

 

For

 

connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation

line

 

 

 

 

 

 

 

 

 

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

55

60

 

 

 

 

 

 

 

 

Fan speed

(rpm)

1400

1300

1200

1100

1000

900

800

- 14 -

Air flow (CMM)

 

Page 15
Image 15
Mitsubishi Electronics PEH-10MYA, PE-8MYC, PE-15MYC, PE-20MYC manual Selection Procedure, Model Selection With actual examples