Mitsubishi Electronics PEH-15MYA, PE-8MYC, PE-15MYC, PE-20MYC, PE-10MYC manual PEH-5,7,8MYA Heat pump

Models: PEH-5MYA PEH-10MYA PE-10MYC PE-20MYC PE-15MYC PEH-15MYA PE-7MYC PEH-20MYA PEH-7MYA PEH-8MYA PE-8MYC

1 115
Download 115 pages 9.76 Kb
Page 10
Image 10

PEH-5,7,8MYA

 

 

 

 

 

 

 

 

Heat pump

Model name

 

 

 

PEH-5MYA

 

 

PEH-7MYA

 

 

PEH-8MYA

Service

 

 

 

PEH-5MYA-EU

 

 

PEH-7MYA-EU

 

 

PEH-8MYA-EU

reference

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply

 

Indoor

 

3PH 4W380~415V 50Hz

 

 

1PH 2W220~240V 50Hz

 

 

3PH 4W380~415V 50Hz

 

 

Outdoor

 

3PH 4W380~415V 50Hz

 

 

3PH 4W380~415V 50Hz

 

 

3PH 4W380~415V 50Hz

Total cooling capacity

 

kW

14.4

 

 

17.9

 

 

22.0

 

 

 

 

 

Btu/h

49,150

 

 

61,100

 

 

75,100

 

 

 

 

 

kcal/h

12,400

 

 

15,400

 

 

18,900

 

Sensible cooling capacity

kW

11.5

 

 

14.3

 

 

17.6

 

 

 

 

 

Btu/h

39,400

 

 

48,800

 

 

60,100

 

 

 

 

 

kcal/h

10,000

 

 

12,300

 

 

15,100

 

Sensible heating capacity

kW

14.4

 

 

18.8

 

 

22.0

 

 

 

 

 

Btu/h

49,150

 

 

64,100

 

 

75,100

 

 

 

 

 

kcal/h

12,400

 

 

16,200

 

 

18,900

 

Capacity step

 

 

%

 

0-100

 

 

 

Refrigerant

 

 

 

 

 

 

R-22

 

 

 

 

Refrigerant charge

 

kg

5.0

 

 

5.7

 

 

6.6

 

Refrigerant control

 

 

 

 

 

Capillary tube

 

Indoor Unit

 

Model name

 

PEH-5MYA

 

 

PEH-7MYA

 

 

PEH-8MYA

 

 

Service

 

PEH-5MYA-EU

 

 

PEH-7MYA-EU

 

 

PEH-8MYA-EU

 

 

reference

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External finish

 

 

 

 

 

 

Galvanized steel

 

Dimension

 

Height

mm

 

428

 

 

 

 

 

 

Width

mm

1,095

 

 

 

 

 

1,415

 

 

 

Depth

mm

 

650

 

 

 

 

Net weight

 

 

kg

60

 

 

67

 

 

70

 

Indoor coil

 

 

 

 

 

 

Cross fin coil

 

 

 

Indoor fan

 

 

 

 

 

 

Centrifugal (Galvanized) - Direct drive

 

Indoor fan motor

 

 

 

Three phase induction motor

Single phase induction motor

 

 

Three phase induction motor

No. Motor output

 

kW

1 0.45

 

 

1 0.21

 

 

1 0.7

 

Indoor fan air flow

 

CMM

42

 

60

 

 

70

 

 

 

 

 

CFM

1,483

 

2,119

 

 

2,472

 

 

 

 

 

L/S

700

 

1,000

 

 

1,167

 

External static

 

 

mmAq

 

12.5

 

 

 

 

pressure

 

 

Pa

 

125

 

 

 

 

Sound pressure level

 

dB(A)

 

55

 

 

56

 

Drain connection

 

 

mm

 

25.4

 

 

 

 

Outdoor unit

 

Model name

 

PUH-5MYE

 

 

PUH-7MYC

 

 

PUH-8MYC

 

PUH-8MYE

 

 

Service

 

PUH-5MYE-EU

 

 

PUH-7MYC1-EU(S)

 

PUH-8MYC1-EU(S)

 

PUH-8MYE-EU

 

 

reference

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External finish

 

 

 

 

 

 

Acrylic resin coating

 

Color

 

 

 

 

 

 

Munsell 5Y 8/1

 

Dimension

 

Height

mm

1,175

 

980

 

 

 

1,175

 

 

Width

mm

1,000

 

1,400

 

 

 

1,250

 

 

Depth

mm

550

 

700

 

 

 

550

Net weight

 

 

kg

150

 

211

 

 

214

 

188

Compressor

 

 

 

 

 

 

Hermetic line start(reciprocating)

 

No. Motor output

 

kW

1 3.73

 

 

 

 

 

1 5.5

 

Outdoor coil

 

 

 

 

 

 

Cross fin coil

 

 

 

Outdoor fan

 

 

 

 

 

 

Propeller-Direct drive

 

Outdoor fan motor

 

 

 

 

 

Three phase induction motor

 

No. Motor output

 

kW

1 0.15

 

 

2 0.09

 

 

1 0.35

Outdoor fan air flow

 

CMM

95

 

167

 

 

 

200

 

 

 

 

CFM

3,355

 

5,898

 

 

 

7,063

 

 

 

 

L/S

1,583

 

2,783

 

 

 

3,333

Sound pressure level

 

dB(A)

57

 

65

 

 

 

65

Protection devices

 

 

High pressure switch, freeze & frost protection, Fuse

 

 

 

 

 

 

 

 

 

Over current relay (comp & indoor fan, outdoor fan)

 

 

 

 

 

 

 

 

 

Internal thermostat (comp & indoor fan, outdoor fan)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note 1. Cooling and heating capacities are based on the following conditions.

 

 

 

 

Cooling

indoor; 27˚CDB, 19˚CWB, outdoor :35˚CDB

 

 

 

 

 

 

 

 

Heating

indoor; 21˚CDB,

outdoor :7.0˚CDB, 6.0˚CWB

 

 

 

 

Cooling and heating capacities are based 5m pipe length.

2.Refergirant charge volumes are factory charged (at 5m piping length).Refrigerant is enclosed with the outdoor unit.

3.Capacity is gross capacity which do not include a deduction for evaporator fan motor heat.

4.The measuring point of the Sound pressure level is 1m from the unit surface.

5.Specification subject to change without notice.

- 9 -