ELECTRICAL OPERATION FLOW CHARTS

PE-7,8,10MYC-EU

PEH-5MYA-EU, PEH-7,8,10MYA-EU

START

POWER ON

CH ON

START

POWER ON

CH ON

30FZ,30CZ ON (SELF HOLD)

SW1

NO

ON?

YES

 

FZ ON

52F ON

MF1 OPERATE

23WA ON?

NO

 

YES

 

 

CZ1,2

ON

 

52C ON

MC OPERATE MF2, 3 OPERATE

CH

OFF

 

SAFETY

NO

DEVICE OFF?

 

YES

 

 

30CZ

OFF

 

52C OFF

MC STOP

MF1 Note

MF2,3 STOP

30FZ,30CZ ON (SELF HOLD)

SW2

NO

ON?

YES

 

FZ ON

52F ON

 

 

MF1 OPERATE

 

SW1 COOL?

NO

 

YES

 

 

23WA ON?

NO

 

YES

 

 

CZ1

ON

 

52C ON

MC OPERATE MF2, 3 OPERATE

CH

OFF

 

SAFETY

NO

DEVICE OFF?

 

YES

 

 

30CZ

OFF

 

HZ1,2 ON

21S4

ON

NO

 

23WA ON?

 

YES

CZ1,2

ON

52C ON

MC OPERATE MF2, 3 OPERATE

 

CH

OFF

 

NO

CONDENSING

 

TEMP

-12

?

YES

26D1, 2 ON

52C

OFF

X1 ON

MC

STOP

X2 ON (SELF HOLD)

MF1

Note

 

CH

MF2,3

STOP

 

 

 

ON

 

21S4 OFF

 

 

 

 

 

SERVICE CALL

 

MF2, 3 STOP

 

 

 

 

 

CH

ON

 

 

 

 

 

NO

CONDENSING

 

SERVICE CALL

TEMP

6

?

 

 

 

 

 

 

 

 

YES

 

 

 

 

26D1, 2 OFF

Note.

1. When the fault of outdoor unit is occurred, the fan(MF1) of indoor unit continues to work. But the unit doesn't work correctly (not cooling and heating ).

Then, turn off the power supply and check outdoor unit.

X1, 2 OFF

21S4 ON

MF2, 3 OPERATE

- 71 -

Page 72
Image 72