(3)Indoor unit and remote controller.(OPTION:PAC-204RC) Connect the wires on the basis of the following wiring diagram.

PEH-5, PE(H)-7,8,10

 

 

 

 

GRAY

TB4

1

 

 

 

F2

 

24VAC(L)

 

 

 

(3.15A)

 

 

 

Tr

 

24VAC(N)

 

 

 

 

 

 

AC

AC24V

COMP1

 

FAN HI

 

 

 

 

220

 

 

TB4

2

3

240V

 

 

 

 

 

 

 

 

 

 

CZ1

FZ

 

GRAY

 

 

 

 

 

 

 

4

 

 

PE(H)-15,20

 

 

 

 

 

 

GRAY

TB3

1

 

 

 

 

F2

 

24VAC(L) COMP1

 

 

 

 

(3.15A)

 

 

 

 

Tr

 

24VAC(N)

 

 

 

AC

AC24V

 

COMP2

FAN HI

 

 

 

 

 

220

 

 

TB3

2

3

4

240V

 

 

 

 

 

 

 

 

 

 

 

CZ

CZ

FZ

 

 

 

1-1

1-2

 

 

GRAY

 

 

 

 

 

 

 

 

5

 

 

 

(4) Wiring example (For metal piping)

 

Power

Breaker

Over current

Earth cable

Control

 

 

cable

 

capacity

protection switch

wiring

 

 

 

 

 

 

 

PEH - 5

2.0mm2

15A

15A

2.0mm2 over

 

 

PE(H) - 7

2.0mm2

15A

15A

2.0mm 2 over

 

 

PE(H) - 8

2.0mm2

15A

15A

2.0mm 2 over

Cable or

 

 

 

 

 

 

 

 

 

 

wire of

 

PE(H) -10

2.0mm2

15A

15A

2.0mm 2over

0.75mm2

 

 

 

 

 

 

(24VDC)

 

PE(H) -15

2.0mm2

30A

30A

2.0mm 2 over

 

PE(H) -20

2.0mm 2

30A

30A

2.0mm 2 over

 

 

PUH - 5

8mm 2

 

50A

50A

8mm 2 over

 

 

PU(H) - 7

8mm 2

 

50A

50A

8mm 2 over

Cable or

The grounding wire must be of the same

 

 

 

 

 

 

 

 

 

diameter as the power cable wires.

PU(H) - 8

8mm

2

 

50A

50A

2

 

 

 

 

8mm over

wire of 2

Table above is an example.

 

 

 

 

 

 

2

 

 

 

2

 

PU(H) -10

14mm

60A

60A

14mm

over

0.75mm

The selection of other capacities should be

 

 

(24VDC)

PU(H) -15

14mm 2

100A

100A

14mm2 over

 

determined in accordance with the relevant

 

 

 

 

 

 

standards.

PU(H) -20

22mm 2

125A

125A

22mm2 over

 

(5) Selecting earth leakage breaker (NV)

To select NF or NV instead of a combination of Class B fuse switch use the following. In the case of Class B fuse rated 15A.

 

Fuse

Earth leakage breaker

 

(class B)

(with over-load protection)

 

 

 

 

 

PEH - 5

15A

NV30-CA

15A

30mA 0.1s or less

 

 

 

 

 

PE(H) - 7

15A

NV30-CA

15A

30mA 0.1s or less

PE(H) - 8

15A

NV30-CA

15A

30mA 0.1s or less

 

 

 

 

 

PE(H) - 10

15A

NV30-CA

15A

30mA 0.1s or less

 

 

 

 

 

PE(H) -15

30A

NV50-CP

30A

30mA 0.1s or less

 

 

 

 

 

PE(H) -20

30A

NV50-CP

30A

30mA 0.1s or less

PUH - 5

50A

NV50-CA

50A

100mA 0.1s or less

PU(H) - 7

50A

NV50-CA

50A

100mA 0.1s or less

PU(H) - 8

50A

NV50-CA

50A

100mA 0.1s or less

 

 

 

 

 

PU(H) - 10

60A

NV60-CA

60A

100mA 0.1s or less

 

 

 

 

 

PU(H) - 15

100A

NV100-CP

100A

100mA 0.1s or less

 

 

 

 

 

PU(H) - 20

125A

NV225-CP

125A

100mA 0.1s or less

NV is a product of

MITSUBISHI ELECTRIC. Table above is an example. The selection of other capacities should be determined in accordance with the relevant standards.

Note.

All electrical wiring must be comply with local electrical authority regulations.

- 101 -