PU-15

(1) At a single installation

The obstacle is on the outlet side. (Fig 1) The obstacle is in four directions. (Fig 2)

ceiling

1500 over

The right and left side and the back and forth side must be opened.

 

300 over

 

However, the outlet

 

500 over side must be opened.

300 over

300 over

 

Service Panel

Fig 1

Fig 2

(2) Relation of unit when many set up unit. (Fig 3,4)

 

 

300over

 

Service-panel

500over

 

 

 

500

 

300 over

over

300 over

Service-panel

Fig 3

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

A A A

Fig 4 All "A" is 500 over.

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

PU-20

(1) At a single installation

The obstacle is on the outlet side. (Fig 1)

The obstacle is in four directions. (Fig 2)

ceiling

1500 over

The right and left side

300 over

 

and the back and forth

 

side must be opened.

 

Fig 1

300 over

However, the outlet side must be opened.

500over

300 over

Service Panel

Fig 2

(2) Relation of unit when many set up unit. (Fig 3,4,5)

 

 

300 over

 

Service-panel

500 over

 

 

300 over

500

300 over

over

Service-panel

If this side is

 

 

 

 

service panel, you

 

 

 

 

need 500 over.

 

 

 

 

If this side is inlet,

A

A

A

A

you need 300 over.

300 over

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

Fig 3

Fig 4 All "A" is 500 over.

If this side is service panel, you need 500 over.

If this side is inlet, you need 300 over.

300 over

A

A

A

300 over

Fig 5 All "A" is 500 over in any case.