Mitsubishi Electronics PEH-10MYA, PE-8MYC, PE-15MYC, PE-20MYC manual Do not wash the unit with water

Models: PEH-5MYA PEH-10MYA PE-10MYC PE-20MYC PE-15MYC PEH-15MYA PE-7MYC PEH-20MYA PEH-7MYA PEH-8MYA PE-8MYC

1 115
Download 115 pages 9.76 Kb
Page 4
Image 4

Caution

Never install on the place where a combustible gas might leak.

The gas may ignite or explode when the gas leaks and collects in surround of the unit.

When the unit is installed at telecommunication centers or hospitals, take a proper provision against noise.

The erroneous operation of air conditioner may be induced by inverter equipment, independent power device, medical equipment or communication equipment.

For special use as for foods, animals/plants, precision equipment or art objects, the applicability should be confirmed beforehand.

As the use for the applications other than that designed originally may result in the deterioration of the quality. Consult your dealer in this regard.

Do not use the unit under a special atmosphere. Installing the unit at the following places may cause a trouble, a place where is much machine oil, salt , humidity or dust, spa district, a place full of sulfur gas, volatile gas, or corrosive gas, a place near high frequency processing machine.

Thermal insulation of the drain pipes is necessary prevent dew condensation.

If the drain pipes are not properly insulated, condensation will result and drip on ceiling, floor or other possessions.

The unit should be securely installed level surface. When the unit inclines, it causes the water leak and the breakdown.

Please confirm the horizontal with the spirit level.

Install drain piping (hose) according to this Installation Manual to ensure proper drainage. Improper drain piping (hose) may cause water leakage and damage to furniture or other possessions.

The unit must be properly earth connected.

Do not connect the earth wire to gas pipe, city water pipe, lightning rod or telephone earth wire.

Improper earth connection may cause electrical shock.

When installing at a watery place, provide an electric leak breaker.

Failure to mount the electric leak breaker may cause electrical shock.

Use breaker or fuse with proper capacity.

Make sure that each appliance has a main power switch.

Using a wire or copper wire instead of proper capacity can cause fire or trouble.

Other appliances connected to the same line could cause an overload.

For the power lines, use standard cables of sufficient current capacity.

Otherwise, current leakage, overheating or fire may occur.

When installing the power lines, do not apply tension to the cables.

The tighten or loosen the connections may cause generate heat and cause fire.

A thing embarrassed which gets wet under the unit is not put.

When the room is high humidity or when the drain pipe is clogged, water may drip from the indoor unit.

Arrange the configuration of wiring not to bring up the panel and terminal cover, and fasten the panel and terminal cover securely.

The poor mounting of the panel or terminal cover may cause the heat generation of the terminal connection, a fire or electrical shock.

Do not wash the unit with water.

If washed with water, electric shock may be caused.

Do not handle the switch with wet hands.

Otherwise electric shock can be resulted.

Be very careful about unit transportation.

The unit should not be carried by only one person if it is more than 20kg. It occasionally causes the damage of the unit and health to be impaired.

Some unit use PP bands for packing. Do not use any PP band for delivery purpose. It may cause the injury.

Do not touch the heat exchanger fins with your bear hands. Doing so may cut your hands.

When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make outdoor unit unstable, resulting in a fall of it.

Be sure to safety dispose the packing materials. Packing materials, such as catches and other metal or wooden parts, may cause stabs or other injuries.

Do not leave the mounting base being damaged.

The damaged base may cause the falling down of the unit which may give injury.

Turn on the main power switch more than 6 hours before starting operation.

Do not turn the main power switch OFF during seasons of heavy use, doing so can result in failure.

Do not touch the compressor or refrigerant piping without wearing glove on your hands.

Touching directly such part can cause a burn or frostbite as it becomes high or low temperature according to the refrigerant state.

Do not touch the metal edges inside the unit without wearing glove on your hands. Touching directly it may injure your hands.

Do not remove the panel or the fan guard from the unit when it is running.

You could be injured if you touch rotating, hot or high- voltage parts.

Do not operate the air conditioner without the air filter set place.

Dust may accumulate, and cause a failure.

At emergency (if you smell something burning), stop operation and turn the power source switch off. Continuing the operation without eliminating the emergency state may cause a machine trouble, fire, or electrical shock.

After stopping operation, be sure to wait for five minutes before turning off the main power switch. Otherwise, water leakage or unit failure may occur.

Remote controller is not installed for the place where direct sunshine strikes.

Remote controller is not pushed with the thing sharpening ahead.

It occasionally causes the electric shock and the break- down.

- 3 -

Page 4
Image 4
Mitsubishi Electronics PEH-10MYA, PE-8MYC, PE-15MYC, PE-20MYC, PE-10MYC, PE-7MYC, PEH-8MYA manual Do not wash the unit with water