MTD ERV 365 Menu P3 ! Set ventilation controls, Menu P4 ! Read off the temperatures % and ppm

Models: ERV 350 ERV 365

1 56
Download 56 pages 39.4 Kb
Page 34
Image 34
Menu P3 ! Set ventilation controls

4

Menu P3 ! Set ventilation controls

 

 

Values for ventilation controls

Sub-menu

Description

Minimum

Maximum

Standard

P30

Setting the power (in %) of the exhaust air

0%

97%

Normal / High

 

fan in position "Absent".

 

 

15% / 15%

P31

Setting the power (in %) of the exhaust air

16%

98%

Normal / High

 

fan in position "Low".

 

 

35% / 40%

P32

Setting the power (in %) of the exhaust air

17%

99%

Normal / High

 

fan in position "Medium".

 

 

50% / 70%

P33

Setting the power (in %) of the exhaust air

18%

100%

Normal / High

 

fan in position "High".

 

 

70% / 90%

P34

Setting the power (in %) of the supply air

0%

97%

Normal / High

 

fan in position "Absent".

 

 

15% / 15%

P35

Setting the power (in %) of the supply air

16%

98%

Normal / High

 

fan in position "Low".

 

 

35% / 40%

P36

Setting the power (in %) of the supply air

17%

99%

Normal / High

 

fan in position "Medium".

 

 

50% / 70%

P37

Setting the power (in %) of the supply air

18%

100%

Normal / High

 

fan in position "High".

 

 

70% / 90%

P38

Current power (in %) of the exhaust air

-

-

Current %

 

fan.

 

 

 

P39

Current power (in %)

-

-

Current %

 

of the supply air fan.

 

 

 

Menu P4 ! Read off the temperatures (% and ppm)

 

 

Read off the temperatures (% and ppm)

Sub-menu

Description

Minimum

Maximum

Standard

P40

Current value of TPOST-HEATER

-

-

Current oC

P41

Comfort temperature

12 oC

28 oC

20 oC

P42

Current value CO2

-

-

Current ppm

P43

Current value relative humidity.

-

-

Current %

P44

Current value of TEXTRACTOR HOOD

-

-

Current oC

P45

Current value of T1

-

-

Current oC

 

(= temperature of the outside air)

 

 

 

P46

Current value of T2

-

-

Current oC

 

(= temperature of the supply air)

 

 

 

P47

Current value of T3

 

 

Current oC

 

(= temperature of the exhaust air)

 

 

 

P48

Current value of T4

 

 

Current oC

 

(= temperature of the stale air)

 

 

 

P49

Current value of TGHE

 

 

Current oC

 

(= temperature of the outside air for geo-

 

 

 

 

thermal heat exchanger)

 

 

 

30 Instructions for the Installer

Page 34
Image 34
MTD ERV 365, ERV 350 manual Menu P3 ! Set ventilation controls, Menu P4 ! Read off the temperatures % and ppm