Menu P3 ! Set ventilation controls
|
| Values for ventilation controls | ||
Description | Minimum | Maximum | Standard | |
P30 | Setting the power (in %) of the exhaust air | 0% | 97% | Normal / High |
| fan in position "Absent". |
|
| 15% / 15% |
P31 | Setting the power (in %) of the exhaust air | 16% | 98% | Normal / High |
| fan in position "Low". |
|
| 35% / 40% |
P32 | Setting the power (in %) of the exhaust air | 17% | 99% | Normal / High |
| fan in position "Medium". |
|
| 50% / 70% |
P33 | Setting the power (in %) of the exhaust air | 18% | 100% | Normal / High |
| fan in position "High". |
|
| 70% / 90% |
P34 | Setting the power (in %) of the supply air | 0% | 97% | Normal / High |
| fan in position "Absent". |
|
| 15% / 15% |
P35 | Setting the power (in %) of the supply air | 16% | 98% | Normal / High |
| fan in position "Low". |
|
| 35% / 40% |
P36 | Setting the power (in %) of the supply air | 17% | 99% | Normal / High |
| fan in position "Medium". |
|
| 50% / 70% |
P37 | Setting the power (in %) of the supply air | 18% | 100% | Normal / High |
| fan in position "High". |
|
| 70% / 90% |
P38 | Current power (in %) of the exhaust air | - | - | Current % |
| fan. |
|
|
|
P39 | Current power (in %) | - | - | Current % |
| of the supply air fan. |
|
|
|
Menu P4 ! Read off the temperatures (% and ppm)
|
| Read off the temperatures (% and ppm) | ||
Description | Minimum | Maximum | Standard | |
P40 | Current value of | - | - | Current oC |
P41 | Comfort temperature | 12 oC | 28 oC | 20 oC |
P42 | Current value CO2 | - | - | Current ppm |
P43 | Current value relative humidity. | - | - | Current % |
P44 | Current value of TEXTRACTOR HOOD | - | - | Current oC |
P45 | Current value of T1 | - | - | Current oC |
| (= temperature of the outside air) |
|
|
|
P46 | Current value of T2 | - | - | Current oC |
| (= temperature of the supply air) |
|
|
|
P47 | Current value of T3 |
|
| Current oC |
| (= temperature of the exhaust air) |
|
|
|
P48 | Current value of T4 |
|
| Current oC |
| (= temperature of the stale air) |
|
|
|
P49 | Current value of TGHE |
|
| Current oC |
| (= temperature of the outside air for geo- |
|
|
|
| thermal heat exchanger) |
|
|
|