4.7.3 Malfunctions (or Problems) without Indications

4

4.7.3 Malfunctions (or Problems) without Indications

This section gives an overview of the malfunctions (or problems) that are not displayed on the CC Ease display.

Problem/Malfunction

Cause

Check / measure

All OFF

Supply voltage

Check the fuse on the PCB panel.

 

 

 

• If the fuse is OK, the circuit board is defec-

 

 

 

 

tive.

 

 

 

 

No supply voltage

The mains power supply has failed.

High air delivery tem-

Bypass remains closed

Lower

perature in summer

 

 

the comfort temperature.

Low air delivery tem-

Bypass remains open

Increase

perature in winter

 

 

the comfort temperature.

No or insufficient air

Filter clogged

Replace

supply, shower re-

 

 

the filters.

mains wet

Valves clogged

Clean

 

 

 

the valves.

 

Heat exchanger clogged by dirt.

Clean

 

 

 

the heat exchanger.

 

Heat exchanger frozen

Thaw

 

 

 

the heat exchanger.

 

Fan dirty

Clean

 

 

 

the fan.

 

Ventilation ducts clogged

Clean

 

MTD-ERV 350 in frost mode

the ventilation ducts.

Too noisy

Fan bearings defective

Replace

 

 

 

the fan bearings.

 

Fan settings

Change

 

 

 

the ventilation control settings.

 

Scraping noise

Install

 

Siphon is empty

the siphon again.

 

• Siphon does not seal

 

 

 

Whistling noise

Seal

 

An air leak somewhere in the system

the air leak.

 

Air flow noises

Install

 

Valves do not seal against duct.

the valves again.

 

Valves not sufficiently open

Set

 

 

 

the valves again.

Leaking condensation

Condensation drain clogged

Clean

 

 

 

the condensation drain.

 

Condensationfromexhaustductdoesnot

Check whether

 

run into drain plate

the connections are correct.

Wired 3-position

Wiring is not OK

Check the circuitry of the 3-position switch

switch does not func-

Switch is defective

using a voltmeter:

tion

 

 

Voltage only on N & L3:

 

 

 

 

[The fans run at position 1].

 

 

 

Voltage only on N & L3 & L2:

 

 

 

 

[The fans run at position 2].

 

 

 

• Voltage only on N & L3 & L1 or N & L3 & L2

 

 

 

 

& L1:

 

 

 

 

[The fans run at position 3].

Wireless 3-position

Battery is discharged

Check

switch does not func-

 

 

the battery.

tion

 

 

Replace the battery, if necessary.

Instructions for the Installer 43