Menu P5 ! Setting additional control functions
|
| Values for additional control functions | ||
Description | Minimum | Maximum | Standard | |
P50 | Activation of | 0 (= No) | 1 (= Yes) | 0 |
| the chimney sweep control system. |
|
|
|
P51 | Indicate whether | 0 (= No) | 1 (= Yes) | 0 |
| preheater is installed. |
|
|
|
|
|
|
|
|
Note:
change only if a preheater was subsequently installed.
If the
• Check the presence of the preheater after a general reset via menu P75.
P52 | Setting the | 0 | 3 | 2 | |
| preheater control. |
|
|
| |
| ϖ | Level 0 |
|
|
|
| ϖ | Particularly safe setting. |
|
|
|
| Level 1 |
|
|
| |
| ϖ | Safe setting. |
|
|
|
| Level 2 |
|
|
| |
| ϖ | Nominal setting. |
|
|
|
| Level 3 |
|
|
| |
|
| Economy setting. |
|
|
|
Note:
ThePREHEATERISSWITCHEDONEARLIESTWITHTHEparticularlysafesetting.Thislevelthusoffersthe greatest safety for maintaining balanced ventilation. On the other hand, the preheater is switchedonthelatestintheECONOMYSETTING.Thislevelthusofferstheleastsafetyformaintain- ing balanced ventilation.
During commissioning of the
LARLY SAFE SETTINGS be selected.
|
|
|
| Values for additional control functions | ||
Description |
| Minimum | Maximum | Standard | ||
P53 | Indicate presence of an extractor hood. |
| 0 (= No) | 1 (= Yes) | 0 | |
| Note: |
|
|
|
| |
| If an extractor hood is connected to the |
|
|
|
| |
| ventilation system, the user can set the |
|
|
|
| |
| ventilation levels for the extractor hood |
|
|
|
| |
| via P29. |
|
|
|
| |
P54 | Indicate presence of a bypass. |
| 0 (= No) | 1 (= Yes) | 1 | |
| Note: |
|
|
|
| |
| The |
|
|
| ||
| passasstandard.Thevaluecantherefore |
|
|
| ||
| be left at '1'. |
|
|
| ||
P55 | Indicate presence of a | 0 (= No) | 1 (= Yes) | 0 | ||
P56 | Setting the necessary air volume for the | nL | HL | nL | ||
| dwelling. |
|
|
| ||
| • | nL: "Normal air volume". |
|
|
| |
| • | HL: "High air volume". |
|
|
|
Note:
Setting the air volume in P56 (to "nL" or "HL") forms the basis for setting the air specifications and hence for setting the fans. For further information, see section 4.5 and P30 to P37.
Instructions for the Installer 31