Multiquip operation manual DCA-600SSV - GENERAL INFORMATION, Generator, Engine Operating Panel

Models: DCA-600SSV

1 108
Download 108 pages 27.16 Kb
Page 20
Image 20
DCA-600SSV — GENERAL INFORMATION

DCA-600SSV — GENERAL INFORMATION

DCA-600SSVWhisperwatt™ Series Familiarization

Generator

The MQ Power Model DCA-600SSV is a 528 kW generator (Figure 5) that is designed as a high quality portable (requires a trailer for transport) power source for telecom sites, lighting facilities, power tools, submersible pumps and other industrial and construction machinery.

Engine Operating Panel

The “Engine Operating Panel” is provided with the following:

Tachometer/Hour Meter Gauge

Water Temperature Gauge / Water Temp. Alarm Lamp

Oil Pressure Gauge / Oil Pressure Alarm Lamp

Charging Alarm Lamp

Fuel Level Gauge / Low Fuel Warning Alarm Lamp

Pre-Heat Button / Pre-Heat Lamp

Air Filter Alarm Lamp

Engine Speed Switch

Battery Switch

Emergency Stop Button

Generator Control Panel

The “Generator Control Panel” is provided with the following:

Frequency Meter (Hz)

AC Ammeter (Amps)

AC Voltmeter (Volts)

Ammeter Change-Over Switch

Voltmeter Change-Over Switch

Voltage Regulator

Panel Light/Panel Light Switch

3-Pole, 1,600 amp Main Circuit Breaker

Engine Control Unit (Computer Controlled)

“Control Box” (Located Behind Gen. Control Panel)

Automatic Voltage Regulator

Current Transformer

Over-Current Relay

Voltage Rectifer

Starter Relay

Voltage Change-over Board

Output Terminal Panel

The “Output Terminal Panel” is provided with the following:

Three 120/240V output receptacles (CS-6369), 50A

Three auxilliary circuit breakers, 50A

Two 120V output receptacles (GFCI), 20A

Two GFCI circuit breakers, 20A

Four output terminal boards (3Ø power)

Ground terminal

Battery Charger (Optional)

Water Heater (Optional)

Open Delta Excitation System

The DCA-600SSV generator is equipped with the state of the art "Open-Delta" excitation system. The open delta system consist of an electrically independent winding wound among stationary windings of the AC output section.

There are four connections of the open delta A, B, C and D. During steady state loads, the power from the voltage regulator is supplied from the parallel connections of A to B, A to D, and C to D. These three phases of the voltage input to the voltage regulator are then rectified and are the excitation current for the exciter section.

When a heavy load, such as a motor starting or a short circuit occurs, the automatic voltage regulator (AVR) switches the configuration of the open delta to the series connection of B to C. This has the effect of adding the voltages of each phase to provide higher excitation to the exciter section and thus better voltage response during the application of heavy loads.

The connections of the AVR to the AC output windings are for sensing only. No power is required from these windings.

The open-delta design provides virtually unlimited excitation current, offering maximum motor starting capabilities. The excitation does not have a "fixed ceiling" and responds according the demands of the required load.

Engine

The DCA-600SSVis powered by a 4 cycle, water cooled, turbocharged VOLVO Model PENTA TAD1642GE Diesel Engine. This engine is designed to meet every performance requirement for the generator. Reference Table 2 for engine specifications.

In keeping with MQ Power's policy of constantly improving its products, the specifications quoted herein are subject to change without prior notice.

Electronic Governor System

The electric governor system controls the RPMs of the en- gine. When the engine demand increases or decreases, the governor system regulates the frequency variation to ±.25%.

Extension Cables

When electric power is to be provided to various tools or loads at some distance from the generator, extension cords are normally used. Cables should be sized to allow for distance in length and amperage so that the voltage drop between the generator and point of use (load) is held to a minimum. Use the cable selection chart (Table 6) as a guide for selecting proper extension cable size.

PAGE 20 — DCA-600SSV — OPERATION AND PARTS MANUAL — REV. #0 (07/13/09)

Page 20
Image 20
Multiquip DCA-600SSV - GENERAL INFORMATION, Engine Operating Panel, Generator Control Panel, Output Terminal Panel