DCA-600SSV — OUTPUT TERMINAL PANEL CONNECTIONS
3Ø-480V UVWO Terminal Output Voltages
1.Jumper the voltage
1Ø-480V UVWO Terminal Output Voltages
1.Make sure the voltage
2.Connect the load wires to the UVWO terminals as shown in Figure 27.
Figure 265 Voltage Change-Over Board
480V Configuration
2.Connect the load wires to the UVWO terminals as shown in Figure 26.
Figure 26. UVWO Terminal Lugs
3Ø-480V Connections
ALWAYS make sure that the
NOTEconnections to the UVWO terminals are secure and tight. The possibility of arcing exists, that could cause a fire.
Figure 27. UVWO Terminal Lugs
1Ø-480V Connections
1Ø-277V UVWO Terminal Output Voltages
1.Make sure the voltage
2.Connect the load wires to the UVWO terminals as shown in Figure 28.
Figure 28. UVWO Terminal Lugs
1Ø-277V Connections
DANGER - UVWO OUTPUT TERMINALS
NEVER attempt to connect a load to the UVWO output terminals while the generator is operating.The possibility exists of serious injury, electrical shock, electrocution even death.