DCA-600SSV — OUTPUT TERMINAL PANEL CONNECTIONS

UVWO Terminal Output Voltages

Various output voltages can be obtained using the UVWO output terminal lugs. The voltages at the terminals are de- pendent on the placement of the jumpers plates (6) on the Voltage Change-Over Board and the adjustment of the Voltage Regulator Control Knob.

Remember the voltage change-over board determines the range of the output voltage and can be configured in two different positions that provide 6 different output voltages at the UVWO output terminals. The generator is shipped from the factory in the 240V configuration. The voltage regulator (VR) allows the user to increase or decrease the selected voltage.

3Ø-240V UVWO Terminal Output Voltages

1.Jumper the voltage change-over board for 240V operation as shown in Figure 20.

Figure 20. Voltage Change-Over Board

240V Configuration

2.Connect the load wires to the UVWO terminals as shown in Figure 21.

Figure 21. UVWO Terminal Lugs

3Ø-240V Connections

3.Turn the voltage regulator knob (Figure 23) clockwise to increase voltage output, turn counterclockwise to decrease voltage output. Use voltage regulator adjustment knob whenever fine tuning of the output voltage is required

Figure 22. Voltage Regulator Knob

1Ø-240V UVWO Terminal Output Voltages

1.Make sure the voltage change-over board is jumpered for 240V operation as shown in Figure 20 .

2.Connect the load wires to the UVWO terminals as shown in Figure 23.

Figure 23. UVWO Terminal Lugs

1Ø-240V Connections

1Ø-139V UVWO Terminal Output Voltages

1.Make sure the voltage change-over board is jumpered for 240V operation as shown in Figure 20.

2.Connect the load wires to the UVWO terminals as shown in Figure 24.

Figure 24. UVWO Terminal Lugs

1Ø-120V Connections

PAGE 32 — DCA-600SSV — OPERATION AND PARTS MANUAL — REV. #0 (07/13/09)

Page 32
Image 32
Multiquip operation manual DCA-600SSV Output Terminal Panel Connections, Uvwo Terminal Output Voltages