DCA-600SSV — GENERATOR START-UP PROCEDURE (AUTO MODE)

DCA-600SSV — GENERATOR START-UP PROCEDURE (AUTO MODE)

23.Observe the generator's ammeter (Figure 61) and verify it reads the anticipated amount of current with respect to the load. The ammeter will only display a current reading if a load is in use.

Figure 61. Ammeter (Load)

24.The generator will run until manually stopped or an abnormal condition occurs.

DANGER - ELECTRICAL SYSTEM HAZARDS

Before connecting this generator to any building’s electrical system, a licensed electrician must install an isolation (transfer) switch. Serious damage to the building’s electrical system may occur without this transfer switch.

CAUTION - BACKUP GENERATOR USE

When connecting the generator to a isolation (transfer) switch, ALWAYS have power applied to the generator's internal battery charger. This will ensure that the engine will not fail due to a dead battery.

WARNING - AUTO MODE MAINTENANCE

When running the generator in the AUTO mode, remember the generator can start up at any time without warning. NEVER attempt to perform any maintenance when the generator is in the auto mode.

CAUTION - ENGINE SPEED SWITCH

The Engine Speed Switch must be set to the "High" position when running in the Auto-Startmode. Failing to set the switch in the proper position can result in damage to your generator when it turns on.

When starting generator in AUTO mode use the "Manual Start-up" procedure except where noted (see below).

1.Perform steps 1 through 4 in the Before Starting section (page 38) as outlined in the Manual Starting Procedure.

2.Set the battery ON/OFF switch (Figure 62) to the “ON” position.

Figure 62. Battery ON/OFF Switch

When the generator is set in the “ AUTO ” mode, the generator will automatically start in the event of

NOTE commercial power falling below a prescribed level by means of a contact closure that is generated automatically by a transfer switch.

3.Set the engine speed switch (Figure 63) to the “High” position.

Figure 63. Engine Speed Switch (High)

4.Place the Off/Manual/Auto switch (Figure 64) on the MPEC unit to the AUTO position.

Figure 64. Off/Manual Auto Switch (AUTO)

5.Press the circuit breaker ON Switch (Figure 58).

6.Verify that the circuit breaker on lamp (Figure 59) is lit.

7.Continue operating the generator as outlined in the Manual Start-upprocedure (start at step 10).

PAGE 42 — DCA-600SSV — OPERATION AND PARTS MANUAL — REV. #0 (07/13/09)