DCA-600SSV— GENERATOR START-UP PROCEDURE (MANUAL)

DCA-600SSV— GENERATOR START-UP PROCEDURE (MANUAL)

16. The ammeter (Figure 54) will indicate zero amps with no 20. Press the main circuit breaker “ON” switch (Figure 58). load applied. When a load is applied, the ammeter will

indicate the amount of current that the load is drawing from the generator.

Figure 54. Ammeter (No Load)

17.The engine oil pressure gauge (Figure 55) will indicate the oil pressure (kg/ cm2) of the engine. Under normal operating conditions the oil pressure is approximately

4

8

0 kg/cm2

ENGINE OIL PRESSURE

Figure 55. Oil Pressure Gauge

18.The coolant temperature gauge (Figure 56) will indicate the coolant temperature. Under normal operating conditions the coolant temperature should be between 167 and 203 degrees Fahrenheit (Green Zone).

Figure 58. Main Circuit Breaker ON Switch

21.Verify that the main circuit breaker “ON” lamp (Figure 59) is lit (ON).

Figure 59. Main Circuit Breaker ON Lamp

22.Place the G.F.C.I. andaux.circuitbreakers(Figure60) in the “OFF” position prior to starting the engine.

WATER

TEMP

Figure 56. Coolant Temperature Gauge

19.The tachometer gauge (Figure 57) will indicate the speed of the engine when the generator is operating. Under normal operating conditions this speed is approximately 1800 RPM’s.

Figure 60. GFCI and Auxiliary Circuit Breakers (ON)

Figure 57. Engine Tachometer Gauge

DCA-600SSV — OPERATION AND PARTS MANUAL — REV. #0 (07/13/09) — PAGE 41