DCA-600SSV — GENERATOR OUTPUTS

Generator OutputVoltages

A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by apply- ing jumpers (6) to the voltage change-over board (Figure 15). To obtain some of the voltages as listed in Table 7 (see below) will require a fine adjustment using the voltage regu- lator (VR) control knob located on the control panel.

Voltage Change-Over Board

The voltage change-over board (Figure 14) is located on the control box, behind the generator control panel. This board has been provided for ease of voltage selection.

Maximum Amps

Table 8 shows the maximum amps the generator can pro- vide. DO NOT exceed the maximum amps as listed.

Table 8.

Maximum Amps

 

 

Model:

DCA600SSV

 

 

Rated

Maximum Amps

Voltage

 

 

 

Single Phase 120

1333.3 amps (4 wire)

Volt

 

 

 

Single Phase 240

666.7 amps (4 wire)

Volt

 

 

 

Three Phase

1443.4 amps

240 Volt

 

 

 

Three Phase

721.7 amps

480 Volt

 

 

 

Figure 14. Voltage Change-Over Board 240V Configuration

DANGER - CHANGING JUMPER PLATES

NEVER attempt to place jumper plates on the voltage change-over board while the generator is in operation.There exists the possibility of electrocution, electrical shock or burn, which can cause severe bodily harm or even death!

Table 7. Generator Available Voltages

Three-Phase

208V 220V 240V 416V 440V

480V

Single-Phase

120V 127V 139V 240V 254V 277V

PAGE 30 — DCA-600SSV — OPERATION AND PARTS MANUAL — REV. #0 (07/13/09)