DCA-600SSV — GENERATOR SHUT-DOWN PROCEDURE
WARNING - SHUTTING DOWNTHE GENERATOR
NEVER stop the engine suddenly except in an emergency.
Normal Shutdown Procedure
To shutdown the generator use the following procedure:
1.Place both the GFCI and AUX circuit breakers as shown in Figure 42 to the OFF position.
2.Place the engine speed switch (Figure 65) in the “LOW ” (down) position.
Figure 65. Engine Speed Switch (Low)
3.Let the engine cool by running it at low speed for
4.Place the MPEC Control Switch (Figure 66) in the OFF/RESET position.
Figure 66. MPEC Control Switch (Off/Reset)
5.Press the main circuit breaker “OFF” switch (Figure 40).
6.Verifythatthemain circuit breaker “OFF” lamp (Figure 41) is lit (ON).
7.Verify that the all status LED on the MPEC display are OFF (not lit).
8.Remove all loads from the generator.
9.Inspect entire generator for any damage or loosening of components that may have occured during operation.
Emergency Shutdown Procedure
1.PUSH inward the emergency stop button located on the engine operating panel (Figure 67) to turn off the generator in the event of an emergency.
EMERGENCYSTOP
PUSH
TO STOP