GENERATOR OUTPUTS

GENERATOR OUTPUTS

Generator Output Voltages

A wide range of voltages are available to supply voltage for many different applications. Voltages are selected by apply-

ing jumpers (6) to the(Figure 16). To obtain some of the voltages as listed in Table 7 (see be- low) will require a fine adjustment using the

(VR)

located on the control panel.

Voltage Change-Over Board

The(Figure 16) is located on the control box, behind the generator control panel. This board has been provided for ease of voltage selection.

Figure 16. Voltage Change-Over Board

Maximum Amps

Table 8 shows the amps the generator can pro- vide. DO NOT exceed the maximum amps as listed.

Table 8. Generator Maximum Amps

Rated Voltage

Maximum Amps

 

 

Single Phase

400 amps (4 wire)

120 Volt

 

 

 

Single Phase

200 amps (4 wire)

240 Volt

 

 

 

Three Phase

433 amps

240 Volt

 

 

 

Three Phase

216 amps

480 Volt

 

 

 

CAUTION - CHANGING VOLTAGES

NEVER attempt to place jumper plates on the

while the generator is in operation. There exist the possibility of

!

Table 7. Voltages Available

Three Phase

208V

220V

240V

416V

440V

480V

(Selectable)

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Phase

120V

127V

139V

240V

254V

277V

(Selectable)

 

 

 

 

 

 

 

 

 

 

 

 

 

PAGE 44 — DCA-180SSJU — OPERATION AND PARTS MANUAL — REV. #3 (02/01/10)