GENERATOR OUTPUTS/ GAUGE READING

How to Read the AC Ammeter and AC Voltage Gauges. The AC ammeter and AC voltmeter gauges are controlled by the AC ammeter and AC voltmeter change-over switches.

Both of these switches are located on the control panel and DO NOT effect the generator output. They are provided to help observe the phase to phase voltage and the current flowing to the load at the UVWO output terminals lugs.

Observe that the voltage change-over board (Figure 17) has been configured for 3Ø, 240V operation.

AC Ammeter Gauge Reading

 

Place the

(Figure 20)

to the U position and observe the current reading (load drain) on the U terminal as indicated on the

(Figure 21). This process can be repeated for terminals V and W.

Figure 20. AC

Figure 21. AC Ammeter

Ammeter

(Amp reading on U lug)

Change-Over Switch

 

 

NOTE

The

gauge will only

Figure 17. Change-Over Board

show a reading when the

 

 

are

(3Ø 240V Configuration)

 

 

 

connected to a load and in use.

 

 

AC Voltmeter Gauge Reading

 

 

 

Place the

(Figure 18)

 

 

in the W-U position and observe the phase to phase voltage

 

 

reading between the W and U terminals as indicated on the

 

 

(Figure 19).

 

 

 

Figure 18. AC

Figure 19. AC Voltmeter

Voltmeter

Gauge

Change-Over Switch

(Volt reading on W-U Lug)

DCA-180SSJU — OPERATION AND PARTS MANUAL — REV. #3 (02/01/10) — PAGE 45